{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50000039015","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50000039015","canonicalUrl":"https://aoctrl.com/abb/3AXD50000039015","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50000039015","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACQ580-01 wall-mounted drive, 0.75 kW, 2.6 A, 380-480 V, IP21, frame size R1.","salesMarkdown":"The ABB 3AXD50000039015 is an ACQ580-01 wall-mounted drive rated 0.75 kW normal-use output (Pn) at 2.6 A (In) on a 380–480 V three-phase supply. Heavy-duty use derates to 0.6 kW (PhD) at 1.8 A (IhD). The 2.6 A normal-use current (In) is the figure to match against your motor nameplate at 400 V. The 0.98 power factor reflects the built-in input rectifier — no external PF correction needed for most installations. IP21 enclosure suits indoor, dry environments. If the installation sees washdown or condensation, you will need a higher IP rating or a separate enclosure. The 40 °C maximum ambient temperature is standard for most control rooms; derate output current if ambient exceeds that. This drive is built for water and wastewater applications — pumping, aeration, filtration. The ACQ580 series includes application-specific features like pump cleaning and flow control algorithms. The wall-mount format and IP21 allow direct mounting in a dry electrical room near the motor. ## Integration notes Wall-mounted with frame size R1 — plan for the gland plate entry at the bottom and clearance for the CAN communication cable. The drive includes the control unit, so no separate controller module is needed. Analog I/O: 2 inputs, 2 outputs. Digital I/O: 6 inputs, 3 outputs. Standby loss is 14 W; factor that into panel cooling.","metaTitle":"ABB 3AXD50000039015 ACQ580-01 Drive, 0.75 kW, 2.6 A","metaDescription":"ABB ACQ580-01 wall-mounted drive, 0.75 kW normal use, 2.6 A, 380-480 V, IP21, active production. Sourced to order via RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"SCIP":"a5c3dd71-8ecd-44d9-98e4-45c53b6836e1 Finland","Altitude":"4000 m","Includes":"Control unit","Frame Size":"R1","Power Factor":"0.98","Sound dB (A)":"59 dB(A)","Standby Loss":"14 W","Analog Inputs":"2","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Wall-mounted","WEEE Category":"5. Small Equipment (No External Dimension More Than 50 cm)","Analog Outputs":"2","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Temperature Rating":"Maximum 40 °C","Enclosure Type NEMA":"Type1","Input Voltage (Uin)":"380 ... 480 V","Degree of Protection":"IP21","Apparent Power Output":"1.8 kV·A","Communication Protocol":"CAN","Power Consumption (@Pcons)":"44 W","Operating Humidity (RHamβ)":"5 ... 95","Multiple Battery Information":"Lithium Coin; CR2032; 220 mAh; 3 V; 1 pc; 3 g","Number of Digital In/Outputs":"6 / 3","Number of Hardware Interfaces":"Industrial Ethernet 0","Output Power, Normal Use (Pn)":"0.75 kW","Output Current, Normal Use (In)":"2.6 A","Output Power, Heavy-Duty Use (PhD)":"0.6 kW","Output Current, Heavy-Duty Use (IhD)":"1.8 A","Output Power, Light-Overload Use (PlD)":"0.75 kW","Certificates and Declarations/RoHS Date":"20240508","Certificates and Declarations/REACH Date":"20250905","Output Current, Light-Overload Use (IlD)":"2.5 A","Certificates and Declarations/RoHS Information":"Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019","Certificates and Declarations/REACH Information":"True - contains substances > 0.1 mass percentage"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50000039015","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50000039015/alternatives.json"},"ai":{"faq":[{"question":"What is the SCIP number for this drive?","answer":"The SCIP number is a5c3dd71-8ecd-44d9-98e4-45c53b6836e1, registered in Finland."},{"question":"What compliance documentation is available?","answer":"RoHS compliance follows EU Directive 2011/65/EU and Amendment 2015/863, with RoHS date 20240508. REACH declaration confirms substances above 0.1 mass percentage, with date 20250905."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50000039015","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50000039015 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}