{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50000039019","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50000039019","canonicalUrl":"https://aoctrl.com/abb/3AXD50000039019","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50000039019","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACQ580-01 LV AC drive, wall-mounted, frame R1, 3-phase 380-480 V, 3 kW / 7.2 A normal duty, IP21, Type 1.","salesMarkdown":"IP21 with NEMA Type 1 enclosure suits indoor installations where dripping water and limited dust are the concern — not washdown or outdoor exposure. Communication is CAN-based; no onboard Industrial Ethernet. The 6 digital inputs and 3 digital outputs, plus 2 analog inputs and 2 analog outputs, give enough I/O for a standalone pump or fan controller without an expansion module. ## Overload duty and efficiency Three duty ratings let you match the drive to the load profile. Light-overload (PlD 3 kW, IlD 6.8 A) covers variable-torque fans and pumps. Normal use (Pn 3 kW, In 7.2 A) is the standard selection for constant-torque applications. Heavy-duty (PhD 2.2 kW, IhD 5.6 A) provides headroom for high-starting-torque loads like conveyors or crushers. Efficiency is rated IE2, which is the baseline for this power class. Standby loss is 14 W; full-load power consumption is 98 W. Power factor at rated load is 0.98. Altitude rating is 4000 m, which covers most installations above sea level without derating. Operating temperature max is 40 °C; humidity range 5 to 95% non-condensing. Sound level is 59 dB(A).","metaTitle":"ABB 3AXD50000039019 ACQ580-01 Drive, 3 kW, 7.2 A, IP21","metaDescription":"ABB ACQ580-01 wall-mounted drive, 3 kW normal use, 7.2 A output, IP21, Type 1. Active production. Sourced to order. RFQ for lead time.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"SCIP":"a5c3dd71-8ecd-44d9-98e4-45c53b6836e1 Finland","Altitude":"4000 m","Includes":"Control unit","Frame Size":"R1","Power Factor":"0.98","Sound dB (A)":"59 dB(A)","Standby Loss":"14 W","Analog Inputs":"2","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Wall-mounted","WEEE Category":"5. Small Equipment (No External Dimension More Than 50 cm)","Analog Outputs":"2","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Temperature Rating":"Maximum 40 °C","Enclosure Type NEMA":"Type1","Input Voltage (Uin)":"380 ... 480 V","Degree of Protection":"IP21","Apparent Power Output":"5.0 kV·A","Communication Protocol":"CAN","Power Consumption (@Pcons)":"98 W","Operating Humidity (RHamβ)":"5 ... 95","Multiple Battery Information":"Lithium Coin; CR2032; 220 mAh; 3 V; 1 pc; 3 g","Number of Digital In/Outputs":"6 / 3","Number of Hardware Interfaces":"Industrial Ethernet 0","Output Power, Normal Use (Pn)":"3 kW","Output Current, Normal Use (In)":"7.2 A","Output Power, Heavy-Duty Use (PhD)":"2.2 kW","Output Current, Heavy-Duty Use (IhD)":"5.6 A","Output Power, Light-Overload Use (PlD)":"3 kW","Certificates and Declarations/RoHS Date":"20240508","Certificates and Declarations/REACH Date":"20250905","Output Current, Light-Overload Use (IlD)":"6.8 A","Certificates and Declarations/RoHS Information":"Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019","Certificates and Declarations/REACH Information":"True - contains substances > 0.1 mass percentage"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50000039019","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50000039019/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings for this drive?","answer":"Normal-use output is 3 kW / 7.2 A; heavy-duty is 2.2 kW / 5.6 A; light-overload is 3 kW / 6.8 A. Input is 380–480 V three-phase, 47.5–63 Hz. Enclosure is IP21 / NEMA Type 1."},{"question":"What is the altitude rating?","answer":"Rated for 4000 m altitude without derating."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50000039019","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50000039019 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}