{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50000039037","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50000039037","canonicalUrl":"https://aoctrl.com/abb/3AXD50000039037","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50000039037","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACQ580-01 series, LV AC wall-mounted drive, 3AXD50000039037, 4 kW normal-use output, 9.4 A, 380-480 V, IP55, frame R1.","salesMarkdown":"It delivers 4 kW normal-use output at 9.4 A from a 380-480 V three-phase supply, with a heavy-duty rating of 3 kW at 7.2 A for tougher load profiles. Three duty classes are defined: normal use (Pn 4 kW, In 9.4 A), light-overload (PlD 4 kW, IlD 8.9 A), and heavy-duty (PhD 3 kW, IhD 7.2 A). The heavy-duty figure governs continuous operation on a pump or fan with a constant-torque component — if your motor nameplate exceeds 7.2 A at the shaft, step up a frame. The normal-use rating matches a standard variable-torque centrifugal load. ## Enclosure, mounting, and environment IP55 with NEMA Type 12 enclosure, wall-mounted, frame size R1. Rated for ambient temperatures up to 40 °C and altitudes to 4000 m — no derating needed at moderate elevation. Operating humidity range 5 to 95 % non-condensing. Standby loss is 14 W; sound level 59 dB(A). The SCIP number is 85773b93-5c45-45c8-a538-ebdaaaf96ece Finland. Two analog inputs and two analog outputs are onboard. Digital I/O counts 6 inputs and 3 outputs. Communication is via CAN; no onboard Industrial Ethernet interface. The control unit is included. Power consumption is 136 W, with an apparent power output of 6.5 kV·A. Power factor is 0.98. Efficiency class IE2.","metaTitle":"ABB 3AXD50000039037 ACQ580-01 Drive, 4 kW, 9.4 A, IP55","metaDescription":"ABB ACQ580-01 wall-mounted drive, 4 kW normal use, 9.4 A output, IP55, Type 12. Active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"SCIP":"85773b93-5c45-45c8-a538-ebdaaaf96ece Finland","Altitude":"4000 m","Includes":"Control unit","Frame Size":"R1","Power Factor":"0.98","Sound dB (A)":"59 dB(A)","Standby Loss":"14 W","Analog Inputs":"2","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Wall-mounted","WEEE Category":"5. Small Equipment (No External Dimension More Than 50 cm)","Analog Outputs":"2","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Temperature Rating":"Maximum 40 °C","Enclosure Type NEMA":"Type12","Input Voltage (Uin)":"380 ... 480 V","Degree of Protection":"IP55","Apparent Power Output":"6.5 kV·A","Communication Protocol":"CAN","Power Consumption (@Pcons)":"136 W","Operating Humidity (RHamβ)":"5 ... 95","Multiple Battery Information":"Lithium Coin; CR2032; 220 mAh; 3 V; 1 pc; 3 g","Number of Digital In/Outputs":"6 / 3","Number of Hardware Interfaces":"Industrial Ethernet 0","Output Power, Normal Use (Pn)":"4 kW","Output Current, Normal Use (In)":"9.4 A","Output Power, Heavy-Duty Use (PhD)":"3 kW","Output Current, Heavy-Duty Use (IhD)":"7.2 A","Output Power, Light-Overload Use (PlD)":"4 kW","Certificates and Declarations/RoHS Date":"20240508","Certificates and Declarations/REACH Date":"20250905","Output Current, Light-Overload Use (IlD)":"8.9 A","Certificates and Declarations/RoHS Information":"Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019","Certificates and Declarations/REACH Information":"True - contains substances > 0.1 mass percentage"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50000039037","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50000039037/alternatives.json"},"ai":{"faq":[{"question":"What are the output ratings for normal and heavy-duty use?","answer":"Normal use: 4 kW, 9.4 A. Heavy-duty use: 3 kW, 7.2 A. Light-overload use: 4 kW, 8.9 A."},{"question":"What enclosure protection does this drive have?","answer":"IP55 with NEMA Type 12, wall-mounted, frame R1."},{"question":"What compliance documentation is available?","answer":"RoHS compliant per EU Directive 2011/65/EU and Amendment 2015/863. REACH declaration confirms substances above 0.1 mass percentage."},{"question":"What is the SCIP number for this drive?","answer":"SCIP: 85773b93-5c45-45c8-a538-ebdaaaf96ece Finland."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50000039037","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50000039037 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}