{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50000042310","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50000042310","canonicalUrl":"https://aoctrl.com/abb/3AXD50000042310","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50000042310","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACS880-14 LV AC industrial regenerative single drive module, IEC: Pn 355 kW, 650 A, 400 V, frame size R11, IP20.","salesMarkdown":"The light-overload rating sits at 618 A (IlD) with the same 355 kW power as normal use, which gives a bit of headroom for occasional peaks without stepping up a frame size. Standby loss is 207 W, and full-load power consumption hits 11039 W at rated output. The efficiency level is IE2, and note that regenerative drives are exempt from EU ecodesign energy efficiency data requirements (Regulation EU/2019/1781, §2.3.c) — so don't expect an IE4 or IE5 label here; the energy recovery is the efficiency story. Operating temperature maxes at +55 °C, humidity 5–95% non-condensing, and altitude up to 4000 m — that's useful if the cabinet sits in a warm plant or at elevation. Sound level is 75 dB(A), so ear protection near the panel is worth planning for. ## Sourcing and integration notes This module includes the control unit, so it's a self-contained regenerative drive — no separate controller card to order. Communication is via CAN; there's no onboard Industrial Ethernet, so if you need PROFINET or EtherNet/IP, plan for an optional fieldbus adapter. Analog I/O: 2 inputs, 2 outputs. Digital I/O: 6 inputs, 2 outputs. The battery information lists two CR2032 lithium coin cells (220 mAh, 3 V) — these back the real-time clock and parameter storage; they'll need replacement every few years in service. Lead time and pricing depend on configuration and quantity, so send the BOM line for a quote. It's a current-production ABB part, so factory lead times apply.","metaTitle":"ABB 3AXD50000042310 ACS880-14 Regenerative Drive, 355 kW, 65","metaDescription":"ABB ACS880-14 regenerative drive module, 355 kW normal use, 650 A output, 380-415 V, IP20, frame R11. Current lifecycle stage. RoHS/REACH compliant. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"SCIP":"c2040ff1-7faf-493e-a1e8-90c1774c7ea5 Finland","Altitude":"4000 m","Includes":"Control unit","Frame Size":"R11","Power Factor":"1.0","Sound dB (A)":"75 dB(A)","Standby Loss":"207 W","Analog Inputs":"2","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Module","WEEE Category":"4. Large Equipment (Any External Dimension More Than 50 cm)","Analog Outputs":"2","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Temperature Rating":"Maximum +55 °C","Ecodesign Exemption":"Energy efficiency data is not provided for the drive. The regenerative drives are exempt from the EU ecodesign requirements (Regulation EU/2019/1781, §2.3.c).","Enclosure Type NEMA":"Open Type","Input Voltage (Uin)":"380 ... 415 V","Degree of Protection":"IP20","Apparent Power Output":"450 kV·A","Communication Protocol":"CAN","Power Consumption (@Pcons)":"11039 W","Operating Humidity (RHamβ)":"5 ... 95","Multiple Battery Information":"Lithium Coin, CR2032, 220 mAh, 3 V, 2 pcs, 6 g","Number of Digital In/Outputs":"6 / 2","Number of Hardware Interfaces":"Industrial Ethernet 0","Output Power, Normal Use (Pn)":"355 kW","Output Current, Normal Use (In)":"650 A","Output Power, Heavy-Duty Use (PhD)":"250 kW","Output Current, Heavy-Duty Use (IhD)":"505 A","Output Power, Light-Overload Use (PlD)":"355 kW","Certificates and Declarations/RoHS Date":"20240508","Certificates and Declarations/REACH Date":"20250905","Output Current, Light-Overload Use (IlD)":"618 A","Certificates and Declarations/RoHS Information":"Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019","Technical UL/Output Power, Heavy-Duty Use (UL)":"NA Hp","Certificates and Declarations/REACH Information":"True - contains substances > 0.1 mass percentage","Technical UL/Output Current, Heavy-Duty Use (UL)":"NA A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50000042310","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50000042310/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings for this drive?","answer":"Normal use: 355 kW, 650 A output. Heavy-duty use: 250 kW, 505 A. Input voltage 380–415 V, 3-phase. Frame size R11, IP20."},{"question":"What compliance documentation is available?","answer":"RoHS compliant per EU Directive 2011/65/EU (date 20240508). REACH compliant (date 20250905), with a declaration that substances above 0.1% mass are present. SCIP number c2040ff1-7faf-493e-a1e8-90c1774c7ea5 Finland. WEEE category 4."},{"question":"What is the altitude rating?","answer":"The drive is rated for installation at altitudes up to 4000 m."},{"question":"How do I source this part?","answer":"This is a current-production ABB drive module sourced to order against an RFQ. Submit your BOM line for a quote; lead time and pricing depend on configuration and quantity."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50000042310","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50000042310 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}