{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50000047499","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50000047499","canonicalUrl":"https://aoctrl.com/abb/3AXD50000047499","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50000047499","rawCanonicalId":null},"summary":{"shortDescription":"ABB drive, frame R3, 380–500 V 3-phase input, 4 kW / 7.6 A normal-duty output, IP21 wall-mounted, current production.","salesMarkdown":"The 3AXD50000047499: The 7.6 A normal-use output current is the number to match against your motor's full-load amps. Light-overload (7.2 A) covers variable-torque fans and centrifugal pumps. Ambient temperature max is +55 °C, with derating above 40 °C typical for this class. Standby loss runs 40 W; full-load power consumption is 219 W. Sound level is 57 dB(A) — quiet enough for a small machine room but not silent. ## Integration notes The drive includes a control unit. Two analog inputs and two analog outputs are available; six digital inputs and two digital outputs. Communication is via CAN — no onboard Industrial Ethernet. Altitude rating 4000 m. Operating humidity 5–95% non-condensing. R3 frame wall-mounted; IP21 enclosure. Internal lithium coin cell (CR2032, 220 mAh, 3 V, two pieces) backs up RTC and parameter storage.","metaTitle":"ABB 3AXD50000047499 VFD, 4 kW, 7.6 A, IP21, R3","metaDescription":"ABB drive 3AXD50000047499: 4 kW normal use, 7.6 A output, IP21, R3 frame. Current production. RoHS/REACH/UL compliant. RFQ for lead time.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Inverter / VFD"],"specifications":{"SCIP":"b32207c2-6d17-418c-84f5-1c59bd7ae46f Finland","Altitude":"4000 m","Includes":"Control unit","Frame Size":"R3","Power Factor":"1.0","Sound dB (A)":"57 dB(A)","Standby Loss":"40 W","Analog Inputs":"2","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Wall-mounted","WEEE Category":"5. Small Equipment (No External Dimension More Than 50 cm)","Analog Outputs":"2","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Temperature Rating":"Maximum +55 °C","Ecodesign Exemption":"Energy efficiency data is not provided for the drive. The regenerative drives are exempt from the EU ecodesign requirements (Regulation EU/2019/1781, §2.3.c).","Enclosure Type NEMA":"Type1","Input Voltage (Uin)":"380 ... 500 V","Degree of Protection":"IP21","Apparent Power Output":"6.6 kV·A","Communication Protocol":"CAN","Power Consumption (@Pcons)":"219 W","Operating Humidity (RHamβ)":"5 ... 95","Multiple Battery Information":"Lithium Coin, CR2032, 220 mAh, 3 V, 2 pcs, 6 g","Number of Digital In/Outputs":"6 / 2","Number of Hardware Interfaces":"Industrial Ethernet 0","Output Power, Normal Use (Pn)":"4 kW","Output Current, Normal Use (In)":"7.6 A","Output Power, Heavy-Duty Use (PhD)":"2.2 kW","Output Current, Heavy-Duty Use (IhD)":"5.2 A","Output Power, Light-Overload Use (PlD)":"4.0 kW","Certificates and Declarations/RoHS Date":"20240508","Certificates and Declarations/REACH Date":"20250905","Output Current, Light-Overload Use (IlD)":"7.2 A","Certificates and Declarations/RoHS Information":"Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019","Technical UL/Output Power, Heavy-Duty Use (UL)":"3.0 Hp","Certificates and Declarations/REACH Information":"True - contains substances > 0.1 mass percentage","Technical UL/Output Current, Heavy-Duty Use (UL)":"5.2 A","Technical UL/Output Power, Light-Overload Use (UL)":"5 Hp","Technical UL/Output Current, Light-Overload Use (UL)":"7.6 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50000047499","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50000047499/alternatives.json"},"ai":{"faq":[{"question":"What compliance documentation does ABB provide for this drive?","answer":"RoHS compliance (EU 2011/65/EU + 2015/863) dated 2024-05-08, REACH declaration dated 2025-09-05, UL listing for North America (3 Hp heavy-duty, 5 Hp light-overload), and SCIP number b32207c2-6d17-418c-84f5-1c59bd7ae46f for EU waste reporting."},{"question":"What is the SCIP number for this drive?","answer":"The SCIP number is b32207c2-6d17-418c-84f5-1c59bd7ae46f, registered in Finland."},{"question":"What are the key output ratings for motor sizing?","answer":"Normal use: 4 kW / 7.6 A. Heavy-duty use: 2.2 kW / 5.2 A. Light-overload use: 4.0 kW / 7.2 A. UL heavy-duty: 3 Hp / 5.2 A. UL light-overload: 5 Hp."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50000047499","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50000047499 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}