{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50000047503","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50000047503","canonicalUrl":"https://aoctrl.com/abb/3AXD50000047503","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50000047503","rawCanonicalId":null},"summary":{"shortDescription":"ABB drive unit, frame size R6, 15 kW / 27 A normal-use output, 380–500 VAC 3-phase input, IP21, IE2 efficiency, current production.","salesMarkdown":"## Drive unit, R6 frame, 15 kW normal duty This ABB 3AXD50000047503 is a wall-mounted drive unit in frame size R6, delivering 15 kW normal-use output at 27 A from a 380–500 V three-phase supply. The heavy-duty rating drops to 11.0 kW at 21 A, while light-overload use holds at 15.0 kW with 26 A — a split that matters when sizing for constant-torque vs variable-torque loads. The IP21 enclosure suits indoor panel mounting; the Type 1 NEMA equivalent means no additional drip shield needed for most control rooms. Two analog inputs and two analog outputs are onboard, plus six digital inputs and two digital outputs. Communication is CAN-based — no onboard Industrial Ethernet, so a separate fieldbus adapter or gateway is required for PROFINET or EtherNet/IP integration. The standby loss of 52 W and power consumption of 533 W at rated load give the panel cooling engineer something to budget for. ## Duty ratings and load profiles The normal-use current of 27 A defines the continuous rating for most pump and fan applications. The apparent power output of 23 kV·A aligns with the 15 kW real-power rating at the listed power factor of 1.0. Wall-mounted installation, IP21, rated for ambient temperatures up to +55 °C and humidity from 5 to 95% non-condensing. Altitude rating of 4000 m means no derating at most common plant elevations. Sound level at 71 dB(A) — noticeable in a quiet control room; factor in ear protection if the drive is near operator stations. The WEEE category 4 (Large Equipment >50 cm) applies for end-of-life disposal in EU markets.","metaTitle":"ABB 3AXD50000047503 Drive Unit, R6, 15 kW, 27 A, IP21","metaDescription":"ABB drive unit, frame size R6, 15 kW normal-use output at 27 A, 380–500 V input, IP21, IE2 efficiency, current lifecycle stage. RoHS/REACH/UL compliance documented. Sourced to orde","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Inverter / VFD"],"specifications":{"SCIP":"b8d4e1da-0951-4e46-943d-fc392c5439e3 Finland","Altitude":"4000 m","Includes":"Control unit","Frame Size":"R6","Power Factor":"1.0","Sound dB (A)":"71 dB(A)","Standby Loss":"52 W","Analog Inputs":"2","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Wall-mounted","WEEE Category":"4. Large Equipment (Any External Dimension More Than 50 cm)","Analog Outputs":"2","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Temperature Rating":"Maximum +55 °C","Ecodesign Exemption":"Energy efficiency data is not provided for the drive. The regenerative drives are exempt from the EU ecodesign requirements (Regulation EU/2019/1781, §2.3.c).","Enclosure Type NEMA":"Type1","Input Voltage (Uin)":"380 ... 500 V","Degree of Protection":"IP21","Apparent Power Output":"23 kV·A","Communication Protocol":"CAN","Power Consumption (@Pcons)":"533 W","Operating Humidity (RHamβ)":"5 ... 95","Multiple Battery Information":"Lithium Coin, CR2032, 220 mAh, 3 V, 2 pcs, 6 g","Number of Digital In/Outputs":"6 / 2","Number of Hardware Interfaces":"Industrial Ethernet 0","Output Power, Normal Use (Pn)":"15 kW","Output Current, Normal Use (In)":"27 A","Output Power, Heavy-Duty Use (PhD)":"11.0 kW","Output Current, Heavy-Duty Use (IhD)":"21 A","Output Power, Light-Overload Use (PlD)":"15.0 kW","Certificates and Declarations/RoHS Date":"20240508","Certificates and Declarations/REACH Date":"20250905","Output Current, Light-Overload Use (IlD)":"26 A","Certificates and Declarations/RoHS Information":"Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019","Technical UL/Output Power, Heavy-Duty Use (UL)":"15.0 Hp","Certificates and Declarations/REACH Information":"True - contains substances > 0.1 mass percentage","Technical UL/Output Current, Heavy-Duty Use (UL)":"21.0 A","Technical UL/Output Power, Light-Overload Use (UL)":"20 Hp","Technical UL/Output Current, Light-Overload Use (UL)":"27 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50000047503","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50000047503/alternatives.json"},"ai":{"faq":[{"question":"What compliance documentation is available for 3AXD50000047503?","answer":"RoHS compliance following EU Directive 2011/65/EU and Amendment 2015/863 (dated 20240508), REACH declaration with substances above 0.1% (dated 20250905), and UL listing for heavy-duty use at 15.0 Hp / 21.0 A and light-overload at 20 Hp."},{"question":"What is the SCIP number for 3AXD50000047503?","answer":"The SCIP number is b8d4e1da-0951-4e46-943d-fc392c5439e3 Finland."},{"question":"What is the maximum operating altitude for this drive?","answer":"The drive is rated for altitudes up to 4000 m."},{"question":"What are the key electrical ratings for 3AXD50000047503?","answer":"Normal-use output is 15 kW at 27 A; heavy-duty is 11.0 kW at 21 A; light-overload is 15.0 kW at 26 A. Input voltage range is 380–500 V three-phase, 47.5–63 Hz. Apparent power output is 23 kV·A at power factor 1.0."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50000047503","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50000047503 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}