{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50000047506","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50000047506","canonicalUrl":"https://aoctrl.com/abb/3AXD50000047506","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50000047506","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACS880 series, 3AXD50000047506, 37 kW normal-use drive, 65 A output, R6 frame, IP21, NEMA 1.","salesMarkdown":"The 3AXD50000047506: Wall-mounted, IP21 with NEMA Type1 enclosure. That means it's suited for indoor, clean environments — no washdown, no dust. The R6 frame is a substantial unit; plan panel layout and gland plate access accordingly. Altitude rated to 4000 m, so installation at elevation doesn't require derating up to that ceiling. ## Communications and I/O Built-in CAN protocol for drive-to-drive or drive-to-controller links. Two analog inputs and two analog outputs are available for speed reference, torque limit, or process feedback. Six digital inputs and two digital outputs cover basic start/stop, fault reset, and status indication. No onboard Industrial Ethernet — if you need PROFINET or EtherNet/IP, plan for an optional fieldbus adapter module.","metaTitle":"ABB 3AXD50000047506 ACS880 Drive, 37 kW, 65 A, R6 Frame","metaDescription":"ABB ACS880 drive, 37 kW normal-use, 65 A output, R6 frame, IP21, NEMA 1. Active production. RoHS/REACH compliant. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Inverter / VFD"],"specifications":{"SCIP":"b8d4e1da-0951-4e46-943d-fc392c5439e3 Finland","Altitude":"4000 m","Includes":"Control unit","Frame Size":"R6","Power Factor":"1.0","Sound dB (A)":"71 dB(A)","Standby Loss":"55 W","Analog Inputs":"2","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Wall-mounted","WEEE Category":"4. Large Equipment (Any External Dimension More Than 50 cm)","Analog Outputs":"2","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Temperature Rating":"Maximum +55 °C","Ecodesign Exemption":"Energy efficiency data is not provided for the drive. The regenerative drives are exempt from the EU ecodesign requirements (Regulation EU/2019/1781, §2.3.c).","Enclosure Type NEMA":"Type1","Input Voltage (Uin)":"380 ... 500 V","Degree of Protection":"IP21","Apparent Power Output":"56 kV·A","Communication Protocol":"CAN","Power Consumption (@Pcons)":"1247 W","Operating Humidity (RHamβ)":"5 ... 95","Multiple Battery Information":"Lithium Coin, CR2032, 220 mAh, 3 V, 2 pcs, 6 g","Number of Digital In/Outputs":"6 / 2","Number of Hardware Interfaces":"Industrial Ethernet 0","Output Power, Normal Use (Pn)":"37 kW","Output Current, Normal Use (In)":"65 A","Output Power, Heavy-Duty Use (PhD)":"30.0 kW","Output Current, Heavy-Duty Use (IhD)":"52 A","Output Power, Light-Overload Use (PlD)":"37.0 kW","Certificates and Declarations/RoHS Date":"20240508","Certificates and Declarations/REACH Date":"20250905","Output Current, Light-Overload Use (IlD)":"62 A","Certificates and Declarations/RoHS Information":"Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019","Technical UL/Output Power, Heavy-Duty Use (UL)":"40.0 Hp","Certificates and Declarations/REACH Information":"True - contains substances > 0.1 mass percentage","Technical UL/Output Current, Heavy-Duty Use (UL)":"52.0 A","Technical UL/Output Power, Light-Overload Use (UL)":"50 Hp","Technical UL/Output Current, Light-Overload Use (UL)":"65 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50000047506","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50000047506/alternatives.json"},"ai":{"faq":[{"question":"What are the key output ratings for this drive?","answer":"Normal-use output is 37 kW at 65 A. Heavy-duty use is 30.0 kW at 52 A. Light-overload use is 37.0 kW at 62 A."},{"question":"What compliance documentation is available?","answer":"RoHS compliance per EU Directive 2011/65/EU and Amendment 2015/863 (date 20240508). REACH declaration confirms substances above 0.1% mass percentage (date 20250905). UL ratings are provided for heavy-duty (40.0 Hp, 52.0 A) and light-overload (50 Hp) use."},{"question":"What is the SCIP number for this drive?","answer":"The SCIP number is b8d4e1da-0951-4e46-943d-fc392c5439e3, registered in Finland."},{"question":"What is the altitude rating?","answer":"Rated for installation up to 4000 m without derating."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50000047506","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50000047506 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}