{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50000047507","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50000047507","canonicalUrl":"https://aoctrl.com/abb/3AXD50000047507","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50000047507","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACS880 drive, 3AXD50000047507, 45 kW normal-use output, 77 A, IP21, R6 frame, wall-mounted, includes control unit.","salesMarkdown":"The ABB 3AXD50000047507 is an R6 frame drive delivering 45 kW normal-use output at 77 A from a 380–500 V three-phase supply. It ships with the control unit included and is wall-mounted with an IP21 / NEMA Type 1 enclosure. ## Duty ratings that matter Normal-use output is 45 kW / 77 A; heavy-duty use drops to 37 kW / 65 A, and light-overload use holds at 45 kW / 73 A. UL ratings mirror the heavy-duty line: 50 Hp / 65 A. Standby loss is 55 W; rated load draws 1661 W. Ambient temperature max is +55 °C. Altitude rating is 4000 m. The control unit provides 2 analog inputs and 2 analog outputs, plus 6 digital inputs and 2 digital outputs. Communication is via CAN; there is no industrial Ethernet interface onboard — if you need PROFINET or EtherNet/IP, plan for an optional fieldbus adapter module. Note the ecodesign exemption: regenerative drives are exempt from EU Regulation 2019/1781 energy-efficiency requirements, so no IE class is published for this unit. The efficiency level listed as IE2 applies to the non-regenerative variant — verify your application's compliance path. ## Sourcing note Active part, quoted to order. The R6 frame and 77 A normal-use rating lock the BOM line — no direct drop-in from a smaller frame. If you need a second-source gate, the R6 is the one for this power class.","metaTitle":"ABB 3AXD50000047507 ACS880 Drive, 45 kW, 77 A, IP21","metaDescription":"ABB 3AXD50000047507 ACS880 drive, 45 kW normal-use, 77 A, IP21, R6 frame. Current lifecycle stage. RoHS/REACH compliant. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Inverter / VFD"],"specifications":{"SCIP":"b8d4e1da-0951-4e46-943d-fc392c5439e3 Finland","Altitude":"4000 m","Includes":"Control unit","Frame Size":"R6","Power Factor":"1.0","Sound dB (A)":"71 dB(A)","Standby Loss":"55 W","Analog Inputs":"2","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Wall-mounted","WEEE Category":"4. Large Equipment (Any External Dimension More Than 50 cm)","Analog Outputs":"2","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Temperature Rating":"Maximum +55 °C","Ecodesign Exemption":"Energy efficiency data is not provided for the drive. The regenerative drives are exempt from the EU ecodesign requirements (Regulation EU/2019/1781, §2.3.c).","Enclosure Type NEMA":"Type1","Input Voltage (Uin)":"380 ... 500 V","Degree of Protection":"IP21","Apparent Power Output":"67 kV·A","Communication Protocol":"CAN","Power Consumption (@Pcons)":"1661 W","Operating Humidity (RHamβ)":"5 ... 95","Multiple Battery Information":"Lithium Coin, CR2032, 220 mAh, 3 V, 2 pcs, 6 g","Number of Digital In/Outputs":"6 / 2","Number of Hardware Interfaces":"Industrial Ethernet 0","Output Power, Normal Use (Pn)":"45 kW","Output Current, Normal Use (In)":"77 A","Output Power, Heavy-Duty Use (PhD)":"37.0 kW","Output Current, Heavy-Duty Use (IhD)":"65 A","Output Power, Light-Overload Use (PlD)":"45.0 kW","Certificates and Declarations/RoHS Date":"20240508","Certificates and Declarations/REACH Date":"20250905","Output Current, Light-Overload Use (IlD)":"73 A","Certificates and Declarations/RoHS Information":"Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019","Technical UL/Output Power, Heavy-Duty Use (UL)":"50.0 Hp","Certificates and Declarations/REACH Information":"True - contains substances > 0.1 mass percentage","Technical UL/Output Current, Heavy-Duty Use (UL)":"65.0 A","Technical UL/Output Power, Light-Overload Use (UL)":"60 Hp","Technical UL/Output Current, Light-Overload Use (UL)":"77 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50000047507","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50000047507/alternatives.json"},"ai":{"faq":[{"question":"What is the SCIP number for this drive?","answer":"The SCIP number is b8d4e1da-0951-4e46-943d-fc392c5439e3, registered in Finland."},{"question":"What compliance documentation is available?","answer":"RoHS compliance follows EU Directive 2011/65/EU and Amendment 2015/863 (date 20240508). REACH confirms substances above 0.1% mass percentage (date 20250905). UL ratings are provided for heavy-duty use: 50 Hp / 65 A."},{"question":"What are the key output ratings?","answer":"Normal-use: 45 kW / 77 A. Heavy-duty: 37 kW / 65 A. Light-overload: 45 kW / 73 A. UL heavy-duty: 50 Hp / 65 A."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50000047507","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50000047507 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}