{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50000047648","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50000047648","canonicalUrl":"https://aoctrl.com/abb/3AXD50000047648","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50000047648","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACS560 series, frame size R2, 11 kW normal-use output, 25 A, 380–480 V three-phase input, IP20, wall-mounted.","salesMarkdown":"The ABB ACS560-01-025A-4 (3AXD50000047648) is an 11 kW variable-frequency drive in frame size R2, rated 25 A for normal-duty motor loads on a 380–480 V three-phase supply. Heavy-duty use drops to 7.5 kW / 17 A, and light-overload use is 11.0 kW / 23.8 A — so the normal-use figure is the one to match against your motor nameplate for continuous duty, while the heavy-duty rating governs applications with higher starting or cyclic overloads. Standby loss of 26 W is the heat the drive dissipates when the motor is not running — relevant for panel thermal calculations and for installations where the drive stays powered continuously but the load cycles. Wall-mounting is the listed method, which matches the frame R2 footprint for a compact panel layout.","metaTitle":"3AXD50000047648 ABB ACS560-01-025A-4 11 kW Drive, 25 A, Fram","metaDescription":"ABB ACS560-01-025A-4 (3AXD50000047648) 11 kW / 25 A normal-use drive, frame size R2, 380–480 V input, IP20, active lifecycle. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"Frame Size":"R2","Standby Loss":"26 W","Frequency (f)":"47 ... 63 Hz","Mounting Type":"Wall-mounted","WEEE Category":"5. Small Equipment (No External Dimension More Than 50 cm)","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Temperature Rating":"Maximum 50 °C","Enclosure Type NEMA":"Open Type","Input Voltage (Uin)":"380 ... 480 V","Degree of Protection":"IP20","Apparent Power Output":"17 kV·A","Output Power, Normal Use (Pn)":"11 kW","Output Current, Normal Use (In)":"25 A","Output Power, Heavy-Duty Use (PhD)":"7.5 kW","Output Current, Heavy-Duty Use (IhD)":"17 A","Output Power, Light-Overload Use (PlD)":"11.0 kW","Output Current, Light-Overload Use (IlD)":"23.8 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50000047648","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50000047648/alternatives.json"},"ai":{"faq":[{"question":"What is the frame size of this drive?","answer":"The frame size is R2, which defines the physical envelope and mounting pattern for panel integration."},{"question":"What is the standby loss of this drive?","answer":"Standby loss is 26 W — the power the drive consumes when the motor is not running, relevant for thermal management in the enclosure."},{"question":"What are the key output ratings for normal and heavy-duty use?","answer":"Normal-use output is 11 kW / 25 A; heavy-duty use is 7.5 kW / 17 A; light-overload use is 11.0 kW / 23.8 A. The normal rating matches continuous motor load, while the heavy-duty rating covers higher overload profiles."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50000047648","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50000047648 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}