{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50000047768","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50000047768","canonicalUrl":"https://aoctrl.com/abb/3AXD50000047768","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50000047768","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACS480 series, general purpose drive module, 3AXD50000047768, 2.2 kW / 5.6 A, 400 V, IP20, frame size R1.","salesMarkdown":"The ABB 3AXD50000047768 is an ACS480-04-05A7-4 general purpose drive module for low-voltage AC motors, rated 2.2 kW normal-use output at 5.6 A on a 380–480 V three-phase supply. Frame size R1, IP20 open-type enclosure, and a maximum ambient of 50 °C. ## Duty ratings and UL derating Normal-use output is 2.2 kW / 5.6 A; heavy-duty use drops to 1.5 kW / 4.0 A, and light-overload use holds at 2.2 kW / 5.3 A. Under UL listing the normal-use current is further derated to 4.8 A, heavy-duty to 3.4 A, and light-overload to 4.8 A — so if the machine nameplate calls for UL compliance, size against the UL column, not the IEC one. ## Power budget and environment Draws 91 W at rated load with 15 W standby loss — the standby figure matters for panel heat calc if the drive spends most of its life idle. Sound level is 63.1 dB(A), which is conversational but not silent; plan enclosure vents accordingly. IP20 means it lives inside a clean cabinet, not on the machine frame. Onboard: 2 analog inputs, 2 analog outputs, 6 digital inputs, 3 digital outputs. Communication is CAN — no onboard Ethernet (0 hardware interfaces for Industrial Ethernet), so if the line uses PROFINET or EtherNet/IP, you will need an optional fieldbus adapter. The control unit is included in the package.","metaTitle":"ABB 3AXD50000047768 ACS480 Drive Module, 2.2 kW, 5.6 A","metaDescription":"ABB ACS480-04-05A7-4 general purpose drive module, 2.2 kW / 5.6 A at 400 V, IP20, frame R1. Active production. RoHS/REACH compliant. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"SCIP":"4b7f0af1-4313-4811-b990-f45b6c1653c8 Finland","Includes":"Control unit","Frame Size":"R1","Sound dB (A)":"63.10 dB(A)","Standby Loss":"15 W","Analog Inputs":"2","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Module","WEEE Category":"5. Small Equipment (No External Dimension More Than 50 cm)","Analog Outputs":"2","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Temperature Rating":"Maximum 50 °C","Enclosure Type NEMA":"Open Type","Input Voltage (Uin)":"380 ... 480 V","Degree of Protection":"IP20","Apparent Power Output":"3.9 kV·A","Communication Protocol":"CAN","Power Consumption (@Pcons)":"91 W","Multiple Battery Information":"Lithium Coin, CR2032, 220 mAh, 3 V, 1 pc, 3 g","Number of Digital In/Outputs":"6 / 3","Number of Hardware Interfaces":"Industrial Ethernet 0","Output Power, Normal Use (Pn)":"2.2 kW","Output Current, Normal Use (In)":"5.6 A","Output Power, Heavy-Duty Use (PhD)":"1.5 kW","Output Current, Heavy-Duty Use (IhD)":"4.0 A","Output Power, Light-Overload Use (PlD)":"2.2 kW","Certificates and Declarations/RoHS Date":"20230315","Certificates and Declarations/REACH Date":"20250905","Output Current, Light-Overload Use (IlD)":"5.3 A","Technical UL/Output Current, Normal Use (UL)":"4.8 A","Certificates and Declarations/RoHS Information":"Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019","Certificates and Declarations/REACH Information":"True - contains substances > 0.1 mass percentage","Technical UL/Output Current, Heavy-Duty Use (UL)":"3.4 A","Technical UL/Output Current, Light-Overload Use (UL)":"4.8 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50000047768","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50000047768/alternatives.json"},"ai":{"faq":[{"question":"What are the key output ratings for this drive module?","answer":"Normal-use output is 2.2 kW at 5.6 A on 380–480 V three-phase. Heavy-duty use is 1.5 kW / 4.0 A. Under UL listing, normal-use current is 4.8 A."},{"question":"What compliance documentation is available for 3AXD50000047768?","answer":"RoHS compliance dated 2023-03-15 per EU Directive 2011/65/EU, REACH compliance dated 2025-09-05, and SCIP number 4b7f0af1-4313-4811-b990-f45b6c1653c8 Finland."},{"question":"Does this drive include the control unit?","answer":"Yes, the control unit is included in the package."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50000047768","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50000047768 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}