{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50000048376","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50000048376","canonicalUrl":"https://aoctrl.com/abb/3AXD50000048376","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50000048376","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACS560 series, 3AXD50000048376, 132 kW normal-use output, 246 A, 380-480 V 3-phase, IP20, R8 frame, wall-mounted.","salesMarkdown":"The ABB 3AXD50000048376 is an ACS560-01-246A-4 drive rated for 132 kW normal-use output at 246 A, with a heavy-duty rating of 110 kW at 206 A. It runs on 380-480 V three-phase, 47-63 Hz, and carries an IP20 enclosure for panel-mount installations. Frame size R8, wall-mounted, with a standby loss of 47 W. Efficiency class IE2. Maximum ambient 40 °C, altitude 1000 m. ## Duty ratings and real load capability The normal-use (light-overload) output is 132 kW at 246 A; heavy-duty use drops to 110 kW at 206 A. That 40 A headroom between light- and heavy-duty curves matters when you're sizing for a continuous conveyor versus a crusher with frequent peak torque demands. The apparent power output of 170 kV·A gives you a quick check against transformer sizing. This drive is listed as Active (current production). No end-of-life notice or successor code is available, so it is a straightforward BOM line for new panels or spares. Wall-mounted, IP20 — intended for clean, dry indoor cabinets. NEMA Open Type means it relies on the surrounding enclosure for additional protection. Ambient limited to 40 °C; derate above that or improve airflow. Altitude rating of 1000 m is standard for lowland installations; above that, expect derating per the drive manual.","metaTitle":"ABB 3AXD50000048376 ACS560 Drive, 132 kW, 246 A, IP20","metaDescription":"ABB ACS560-01-246A-4 drive, 132 kW normal-use output, 246 A, 380-480 V 3-phase, IP20, R8 frame, active production. Sourced to order via RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"Altitude":"1000 m","Frame Size":"R8","Standby Loss":"47 W","Frequency (f)":"47 ... 63 Hz","Mounting Type":"Wall-mounted","WEEE Category":"4. Large Equipment (Any External Dimension More Than 50 cm)","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Temperature Rating":"Maximum 40 °C","Enclosure Type NEMA":"Open Type","Input Voltage (Uin)":"380 ... 480 V","Degree of Protection":"IP20","Apparent Power Output":"170 kV·A","Output Power, Normal Use (Pn)":"132 kW","Output Current, Normal Use (In)":"246 A","Output Power, Heavy-Duty Use (PhD)":"110 kW","Output Current, Heavy-Duty Use (IhD)":"206 A","Output Power, Light-Overload Use (PlD)":"132 kW","Output Current, Light-Overload Use (IlD)":"234 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50000048376","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50000048376/alternatives.json"},"ai":{"faq":[{"question":"What is the frame size and mounting?","answer":"Frame size R8, wall-mounted. IP20 enclosure for panel installation."},{"question":"What are the key output ratings?","answer":"Normal-use: 132 kW, 246 A. Heavy-duty: 110 kW, 206 A. Light-overload: 132 kW, 234 A. Apparent power: 170 kV·A."},{"question":"What input voltage and frequency does it accept?","answer":"380-480 V three-phase, 47-63 Hz."},{"question":"What is the ambient temperature and altitude limit?","answer":"Maximum 40 °C ambient, altitude 1000 m without derating."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50000048376","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50000048376 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}