{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50000049032","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50000049032","canonicalUrl":"https://aoctrl.com/abb/3AXD50000049032","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50000049032","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACH580-07 cabinet-built drive, 3AXD50000049032, 132 kW normal duty, 246 A output, BACnet, IP21, frame R8.","salesMarkdown":"The ABB 3AXD50000049032 is an ACH580-07 cabinet-built LV AC drive for HVAC applications, rated 132 kW normal use at 246 A output on a 380–480 V three-phase supply. Frame size R8, IP21 enclosure, Type 1. BACnet is the onboard fieldbus — no separate gateway needed for BMS integration. Normal-use (light-overload) output is 132 kW / 246 A; heavy-duty use drops to 110 kW / 206 A. That 40 A difference matters when the load profile includes sustained overloads — centrifugal fans and pumps usually stay in the normal-use band, but conveyors or screw compressors push into heavy-duty territory. UL ratings mirror the pattern: 200 Hp / 240 A light-overload, 150 Hp / 180 A heavy-duty. ## Integration notes Cabinet-built — ships as a complete unit with the control module included. Two analog inputs and two analog outputs are on board; six digital inputs and three digital outputs handle basic I/O. The BACnet interface is fixed at the factory; no Industrial Ethernet port is populated. Ambient temperature max 40 °C, humidity 5–95% non-condensing. Sound pressure level 65 dB(A) at full load. The internal lithium coin cell (CR2032, 220 mAh) backs the real-time clock.","metaTitle":"ABB 3AXD50000049032 ACH580-07 Drive, 132 kW, 246 A, BACnet","metaDescription":"ABB ACH580-07 cabinet-built drive, 132 kW normal use, 246 A output, BACnet communication, IP21, active production, RoHS/REACH compliant. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"SCIP":"182c528b-29d6-4b33-89d3-2ec8b482ca1d Finland","title":"3AXD50000049032","Includes":"Control unit","Frame Size":"R8","description":"LV AC cabinet-built drive for HVAC, IEC: Pn 132 kW, 246 A, 400 V, UL: Pld 200 Hp, 240 A, 480 V (ACH580-07-0246A-4)","Sound dB (A)":"65 dB(A)","Analog Inputs":"2","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Cabinet-built","WEEE Category":"4. Large Equipment (Any External Dimension More Than 50 cm)","Analog Outputs":"2","lifecycle_stage":"current","Number of Phases":"3-phase","Temperature Rating":"Maximum 40 °C","Ecodesign Exemption":"Energy efficiency data is not provided for this cabinet-based drive. Cabinet built drives, with already conform modules, are excluded from the scope of the EU ecodesign requirements (Regulation EU/2019/1781, §2.3.e).","Enclosure Type NEMA":"Type1","Input Voltage (Uin)":"380 ... 480 V","Degree of Protection":"IP21","Apparent Power Output":"170 kV·A","Communication Protocol":"BACNET","Power Consumption (@Pcons)":"3806 W","Operating Humidity (RHamβ)":"5 to 95%","Multiple Battery Information":"Lithium Coin, CR2032, 220 mAh, 3 V, 1 pc, 3 g","Number of Digital In/Outputs":"6 / 3","Number of Hardware Interfaces":"Industrial Ethernet 0","Output Power, Normal Use (Pn)":"132 kW","Output Current, Normal Use (In)":"246 A","Output Power, Heavy-Duty Use (PhD)":"110 kW","Output Current, Heavy-Duty Use (IhD)":"206 A","Output Power, Light-Overload Use (PlD)":"132 kW","Certificates and Declarations/RoHS Date":"20240508","Certificates and Declarations/REACH Date":"20250905","Output Current, Light-Overload Use (IlD)":"234 A","Certificates and Declarations/RoHS Information":"Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019","Technical UL/Output Power, Heavy-Duty Use (UL)":"150 Hp","Certificates and Declarations/REACH Information":"True - contains substances > 0.1 mass percentage","Technical UL/Output Current, Heavy-Duty Use (UL)":"180 A","Technical UL/Output Power, Light-Overload Use (UL)":"200 Hp","Technical UL/Output Current, Light-Overload Use (UL)":"240 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/8350d8d31ab69a2442cfc895a8016b73.pdf","sourceUrl":"https://www.abb.com/global/en/products/3axd50000049032"},"ai":{"faq":[{"question":"What compliance documentation does this drive carry?","answer":"RoHS compliant per EU Directive 2011/65/EU (date 20240508), REACH registered (date 20250905), UL listed with heavy-duty and light-overload HP ratings. SCIP number 182c528b-29d6-4b33-89d3-2ec8b482ca1d Finland."},{"question":"What is the SCIP number for this part?","answer":"182c528b-29d6-4b33-89d3-2ec8b482ca1d Finland."},{"question":"Does the drive include a control unit?","answer":"Yes, the control unit is included as part of the cabinet-built assembly."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50000049032","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50000049032 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}