{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50000049033","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50000049033","canonicalUrl":"https://aoctrl.com/abb/3AXD50000049033","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50000049033","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACH580-07 cabinet-built drive, 3AXD50000049033, 160 kW normal use, 293 A, 380-480 V, IP21, Type 1, BACnet, active production.","salesMarkdown":"The 3AXD50000049033: This drive ships with the control unit included — no separate ordering for the control board. Two analog inputs and two analog outputs are built in; six digital inputs and three digital outputs are on the terminal block. No industrial Ethernet port (0 hardware interfaces), so BACnet MS/TP is the fieldbus slice. The lithium coin cell (CR2032, 220 mAh) backs the real-time clock. Cabinet-built — mounts as a standalone enclosure, not a panel-mount module. Ambient temperature maximum 40 °C; operating humidity 5 to 95% non-condensing. Sound pressure 65 dB(A) at rated load. Power consumption at rated output is 4942 W; apparent power output 203 kV·A. Ecodesign exemption applies per EU/2019/1781 §2.3.e — no energy-efficiency data required for cabinet-built drives with conform modules.","metaTitle":"ABB 3AXD50000049033 ACH580-07 HVAC Drive, 160 kW, 293 A","metaDescription":"ABB ACH580-07 cabinet-built drive, 160 kW normal use, 293 A, 380-480 V, IP21, Type 1, BACnet, active production. RoHS/REACH/UL compliance on file. RFQ for lead time.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"SCIP":"182c528b-29d6-4b33-89d3-2ec8b482ca1d Finland","title":"3AXD50000049033","Includes":"Control unit","Frame Size":"R8","description":"LV AC cabinet-built drive for HVAC, IEC: Pn 160 kW, 293 A, 400 V, UL: Pld 200 Hp, 260 A, 480 V (ACH580-07-0293A-4)","Sound dB (A)":"65 dB(A)","Analog Inputs":"2","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Cabinet-built","WEEE Category":"4. Large Equipment (Any External Dimension More Than 50 cm)","Analog Outputs":"2","lifecycle_stage":"current","Number of Phases":"3-phase","Temperature Rating":"Maximum 40 °C","Ecodesign Exemption":"Energy efficiency data is not provided for this cabinet-based drive. Cabinet built drives, with already conform modules, are excluded from the scope of the EU ecodesign requirements (Regulation EU/2019/1781, §2.3.e).","Enclosure Type NEMA":"Type1","Input Voltage (Uin)":"380 ... 480 V","Degree of Protection":"IP21","Apparent Power Output":"203 kV·A","Communication Protocol":"BACNET","Power Consumption (@Pcons)":"4942 W","Operating Humidity (RHamβ)":"5 to 95%","Multiple Battery Information":"Lithium Coin, CR2032, 220 mAh, 3 V, 1 pc, 3 g","Number of Digital In/Outputs":"6 / 3","Number of Hardware Interfaces":"Industrial Ethernet 0","Output Power, Normal Use (Pn)":"160 kW","Output Current, Normal Use (In)":"293 A","Output Power, Heavy-Duty Use (PhD)":"132 kW","Output Current, Heavy-Duty Use (IhD)":"246 A","Output Power, Light-Overload Use (PlD)":"160 kW","Certificates and Declarations/RoHS Date":"20240508","Certificates and Declarations/REACH Date":"20250905","Output Current, Light-Overload Use (IlD)":"278 A","Certificates and Declarations/RoHS Information":"Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019","Technical UL/Output Power, Heavy-Duty Use (UL)":"150 Hp","Certificates and Declarations/REACH Information":"True - contains substances > 0.1 mass percentage","Technical UL/Output Current, Heavy-Duty Use (UL)":"240 A","Technical UL/Output Power, Light-Overload Use (UL)":"200 Hp","Technical UL/Output Current, Light-Overload Use (UL)":"260 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/af306990422f2e7c7e988ecb5e546d49.pdf","sourceUrl":"https://www.abb.com/global/en/products/3axd50000049033"},"ai":{"faq":[{"question":"What compliance documentation is available for this drive?","answer":"RoHS compliance dated 20240508 per EU Directive 2011/65/EU; REACH compliance dated 20250905 (contains substances > 0.1 mass percentage); SCIP number 182c528b-29d6-4b33-89d3-2ec8b482ca1d Finland. UL ratings are listed for heavy-duty and light-overload use."},{"question":"What are the key ratings for normal and heavy-duty use?","answer":"Normal use: 160 kW, 293 A output. Heavy-duty use: 132 kW, 246 A. Light-overload use: 160 kW, 278 A. UL light-overload: 200 Hp, 260 A; UL heavy-duty: 150 Hp, 240 A."},{"question":"What is the SCIP number for this drive?","answer":"SCIP: 182c528b-29d6-4b33-89d3-2ec8b482ca1d Finland."},{"question":"Does the drive include a control unit?","answer":"Yes, the control unit is included with the drive."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50000049033","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50000049033 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}