{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50000049034","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50000049034","canonicalUrl":"https://aoctrl.com/abb/3AXD50000049034","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50000049034","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACH580-07 LV AC cabinet-built drive, 3AXD50000049034, 200 kW normal use, 363 A, 380–480 V, IP21, BACnet, frame R9.","salesMarkdown":"The 3AXD50000049034: Heavy-duty use rating is 160 kW at 293 A; light-overload use is 200 kW at 345 A. UL heavy-duty output is 250 Hp at 302 A, light-overload UL is 300 Hp at 361 A. Apparent power output is 251 kV·A. ## Integration checklist Cabinet-built drive — mounts as a standalone enclosure, not a chassis module for a panel. Includes the control unit. Two analog inputs and two analog outputs are available; digital I/O is 6 inputs and 3 outputs. No industrial Ethernet port — BACnet only for building automation integration. Power consumption at rated load is 5868 W. Frequency range is 47.5–63 Hz. Operating humidity 5–95% non-condensing. Sound level is 68 dB(A). Contains a CR2032 lithium coin cell (220 mAh, 3 V) for backup.","metaTitle":"ABB 3AXD50000049034 ACH580-07 Cabinet Drive, 200 kW, 363 A","metaDescription":"ABB 3AXD50000049034 ACH580-07 LV AC cabinet-built drive, 200 kW normal use, 363 A, 380–480 V, IP21, BACnet, active production. RFQ for lead time.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"SCIP":"105dd15e-a9d4-40aa-a399-53b46cd95cf3 Finland","title":"3AXD50000049034","Includes":"Control unit","Frame Size":"R9","description":"LV AC cabinet-built drive for HVAC, IEC: Pn 200 kW, 363 A, 400 V, UL: Pld 300 Hp, 361 A, 480 V (ACH580-07-0363A-4)","Sound dB (A)":"68 dB(A)","Analog Inputs":"2","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Cabinet-built","WEEE Category":"4. Large Equipment (Any External Dimension More Than 50 cm)","Analog Outputs":"2","lifecycle_stage":"current","Number of Phases":"3-phase","Temperature Rating":"Maximum 40 °C","Ecodesign Exemption":"Energy efficiency data is not provided for this cabinet-based drive. Cabinet built drives, with already conform modules, are excluded from the scope of the EU ecodesign requirements (Regulation EU/2019/1781, §2.3.e).","Enclosure Type NEMA":"Type1","Input Voltage (Uin)":"380 ... 480 V","Degree of Protection":"IP21","Apparent Power Output":"251 kV·A","Communication Protocol":"BACNET","Power Consumption (@Pcons)":"5868 W","Operating Humidity (RHamβ)":"5 to 95%","Multiple Battery Information":"Lithium Coin, CR2032, 220 mAh, 3 V, 1 pc, 3 g","Number of Digital In/Outputs":"6 / 3","Number of Hardware Interfaces":"Industrial Ethernet 0","Output Power, Normal Use (Pn)":"200 kW","Output Current, Normal Use (In)":"363 A","Output Power, Heavy-Duty Use (PhD)":"160 kW","Output Current, Heavy-Duty Use (IhD)":"293 A","Output Power, Light-Overload Use (PlD)":"200 kW","Certificates and Declarations/RoHS Date":"20240508","Certificates and Declarations/REACH Date":"20250905","Output Current, Light-Overload Use (IlD)":"345 A","Certificates and Declarations/RoHS Information":"Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019","Technical UL/Output Power, Heavy-Duty Use (UL)":"250 Hp","Certificates and Declarations/REACH Information":"True - contains substances > 0.1 mass percentage","Technical UL/Output Current, Heavy-Duty Use (UL)":"302 A","Technical UL/Output Power, Light-Overload Use (UL)":"300 Hp","Technical UL/Output Current, Light-Overload Use (UL)":"361 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/7d2ecac4f3d87ac91236c983dbba284f.pdf","sourceUrl":"https://www.abb.com/global/en/products/3axd50000049034"},"ai":{"faq":[{"question":"What compliance documentation does ABB provide for this drive?","answer":"RoHS compliant per EU Directive 2011/65/EU and Amendment 2015/863 (date 20240508). REACH declaration confirms substances above 0.1 mass percentage (date 20250905). SCIP number 105dd15e-a9d4-40aa-a399-53b46cd95cf3 Finland. WEEE category 4. Ecodesign exemption applies per EU 2019/1781."},{"question":"What are the key ratings for this drive?","answer":"Normal-use output: 200 kW, 363 A. Heavy-duty: 160 kW, 293 A. Light-overload: 200 kW, 345 A. UL heavy-duty: 250 Hp, 302 A; UL light-overload: 300 Hp, 361 A. Input 380–480 V, 3-phase, 47.5–63 Hz. Apparent power 251 kV·A."},{"question":"What communication protocol does this drive use?","answer":"BACnet is the onboard protocol. No industrial Ethernet interface on this variant."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50000049034","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50000049034 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}