{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50000049038","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50000049038","canonicalUrl":"https://aoctrl.com/abb/3AXD50000049038","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50000049038","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACQ580-07-0206A-4, LV AC cabinet-built drive, 110 kW / 206 A normal use, 380-480 V, IP21, Type 1, frame R7.","salesMarkdown":"The 3AXD50000049038: The normal-use output current of 206 A (In) is the rating for continuous duty at 110 kW. For heavy-duty cycles — higher starting torque or overload — the drive is rated 169 A (IhD) at 90 kW. Light-overload use is rated 196 A (IlD) at 110 kW. Under UL listing, heavy-duty output is 125 Hp at 156 A, and light-overload is 150 Hp at 180 A. The apparent power output is 143 kV·A. These numbers define the motor frame size and cable cross-section you need; the drive itself is frame R7. Enclosure is IP21 with NEMA Type 1, suitable for indoor cabinet installation. Ambient temperature is rated to 40 °C maximum, with operating humidity 5-95% non-condensing. The drive includes a control unit and a lithium coin cell (CR2032, 220 mAh) for backup. The drive provides 2 analog inputs, 2 analog outputs, and 6 digital inputs / 3 digital outputs. Communication is via CAN bus; there are no industrial Ethernet interfaces on this variant. Power consumption at rated load is 3314 W, with a power factor of 0.98.","metaTitle":"3AXD50000049038 ABB ACQ580-07-0206A-4 LV AC Cabinet-Built Dr","metaDescription":"ABB ACQ580-07-0206A-4 LV AC cabinet-built drive for water & wastewater, 110 kW / 206 A normal use, 380-480 V, IP21, Type 1, current production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"SCIP":"f8697513-3243-4f24-9777-7dbe1d791662 Finland","Includes":"Control unit","Frame Size":"R7","Power Factor":"0.98","Sound dB (A)":"67 dB(A)","Analog Inputs":"2","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Cabinet-built","WEEE Category":"4. Large Equipment (Any External Dimension More Than 50 cm)","Analog Outputs":"2","lifecycle_stage":"current","Number of Phases":"3-phase","Temperature Rating":"Maximum 40 °C","Ecodesign Exemption":"Energy efficiency data is not provided for this cabinet-based drive. Cabinet built drives, with already conform modules, are excluded from the scope of the EU ecodesign requirements (Regulation EU/2019/1781, §2.3.e).","Enclosure Type NEMA":"Type1","Input Voltage (Uin)":"380 ... 480 V","Degree of Protection":"IP21","Apparent Power Output":"143 kV·A","Communication Protocol":"CAN","Power Consumption (@Pcons)":"3314 W","Operating Humidity (RHamβ)":"5 ... 95","Multiple Battery Information":"Lithium Coin, CR2032, 220 mAh, 3 V, 1 pc, 3 g","Number of Digital In/Outputs":"6 / 3","Number of Hardware Interfaces":"Industrial Ethernet 0","Output Power, Normal Use (Pn)":"110 kW","Output Current, Normal Use (In)":"206 A","Output Power, Heavy-Duty Use (PhD)":"90 kW","Output Current, Heavy-Duty Use (IhD)":"169 A","Output Power, Light-Overload Use (PlD)":"110 kW","Certificates and Declarations/RoHS Date":"20240508","Certificates and Declarations/REACH Date":"20250905","Output Current, Light-Overload Use (IlD)":"196 A","Certificates and Declarations/RoHS Information":"Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019","Technical UL/Output Power, Heavy-Duty Use (UL)":"125 Hp","Certificates and Declarations/REACH Information":"True - contains substances > 0.1 mass percentage","Technical UL/Output Current, Heavy-Duty Use (UL)":"156 A","Technical UL/Output Power, Light-Overload Use (UL)":"150 Hp","Technical UL/Output Current, Light-Overload Use (UL)":"180 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50000049038","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50000049038/alternatives.json"},"ai":{"faq":[{"question":"What compliance documentation does this drive have?","answer":"RoHS compliant per EU Directive 2011/65/EU and Amendment 2015/863 (date 20240508). REACH declaration confirms substances above 0.1 mass percentage (date 20250905). SCIP number f8697513-3243-4f24-9777-7dbe1d791662 Finland."},{"question":"What are the key ratings for this drive?","answer":"Normal-use output: 110 kW / 206 A. Heavy-duty: 90 kW / 169 A. Light-overload: 110 kW / 196 A. Input: 380-480 V three-phase, 47.5-63 Hz. Apparent power: 143 kV·A."},{"question":"What is the enclosure rating?","answer":"IP21, NEMA Type 1, for indoor cabinet installation."},{"question":"What communication protocol does it use?","answer":"CAN bus. No industrial Ethernet interfaces are included."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50000049038","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50000049038 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}