{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50000049062","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50000049062","canonicalUrl":"https://aoctrl.com/abb/3AXD50000049062","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50000049062","rawCanonicalId":null},"summary":{"shortDescription":"ABB drive module, R11 frame, 450 kW normal-use, 820 A output, IP00 open type, 380-480 V 3-phase input.","salesMarkdown":"The ABB 3AXD50000049062 is an R11-frame drive module rated for 450 kW normal-use output and 820 A continuous current. It takes 380-480 V three-phase input at 47.5-63 Hz and delivers 568 kVA apparent power. The heavy-duty rating is 355 kW at 625 A, and the light-overload rating matches the normal-use power at 450 kW with 810 A output. This is a current-production part — no phase-out or last-time-buy to plan around. The three duty ratings let you match the drive to the application without over-specifying. Normal use (450 kW, 820 A) covers constant-torque loads like conveyors and pumps running at full nameplate. Heavy-duty use (355 kW, 625 A) applies to higher-torque profiles — crushers, extruders, or any application where the motor draws more current per kW. Light-overload use (450 kW, 810 A) is for variable-torque loads like fans and centrifugal pumps where peak current is brief. The UL ratings track identically: 700 Hp normal-use, 500 Hp heavy-duty, with the same current figures. ## Physical and environmental constraints The module is IP00 open type, so it needs a clean, dry enclosure — no washdown areas or dusty environments without a proper cabinet. Maximum ambient temperature is 40 °C, and the altitude rating is 1000 m without derating. Operating humidity range is 5-95% RH. Standby loss is 466 W, which adds to the cabinet heat load. Sound level is 72 dB(A) — noticeable in a quiet room but typical for an R11 frame at full load. The unit includes a control module and a lithium coin cell (CR2032, 220 mAh) for parameter backup. The drive communicates via CAN bus. It has 2 analog inputs, 2 analog outputs, and 6 digital inputs plus 3 digital outputs. There are no built-in Industrial Ethernet interfaces on this module — any network connectivity requires an optional fieldbus adapter. The 6/3 digital I/O count is enough for basic start/stop, speed reference, and fault feedback without an external I/O block.","metaTitle":"ABB 3AXD50000049062 Drive Module, 450 kW, 820 A, R11","metaDescription":"ABB drive module 3AXD50000049062, 450 kW normal-use, 820 A output, R11 frame, IP00 open type. Active production. Sourced to order. RoHS/REACH compliant.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"SCIP":"e9fd22a6-81c4-4079-87c1-83e8cf566d7a Finland","Altitude":"1000 m","Includes":"Control unit","Frame Size":"R11","Power Factor":"0.98","Sound dB (A)":"72 dB(A)","Standby Loss":"466 W","Analog Inputs":"2","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Module","WEEE Category":"4. Large Equipment (Any External Dimension More Than 50 cm)","Analog Outputs":"2","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Temperature Rating":"Maximum 40 °C","Enclosure Type NEMA":"Open Type","Input Voltage (Uin)":"380 ... 480 V","Degree of Protection":"IP00","Apparent Power Output":"568 kV·A","Communication Protocol":"CAN","Power Consumption (@Pcons)":"9652 W","Operating Humidity (RHamβ)":"5 ... 95","Multiple Battery Information":"Lithium Coin, CR2032, 220 mAh, 3 V, 1 pc, 3 g","Number of Digital In/Outputs":"6 / 3","Number of Hardware Interfaces":"Industrial Ethernet 0","Output Power, Normal Use (Pn)":"450 kW","Output Current, Normal Use (In)":"820 A","Output Power, Heavy-Duty Use (PhD)":"355 kW","Output Current, Heavy-Duty Use (IhD)":"625 A","Output Power, Light-Overload Use (PlD)":"450 kW","Certificates and Declarations/RoHS Date":"20240508","Certificates and Declarations/REACH Date":"20250905","Output Current, Light-Overload Use (IlD)":"810 A","Technical UL/Output Power, Normal Use (UL)":"700 Hp","Technical UL/Output Current, Normal Use (UL)":"820 A","Certificates and Declarations/RoHS Information":"Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019","Technical UL/Output Power, Heavy-Duty Use (UL)":"500 Hp","Certificates and Declarations/REACH Information":"True - contains substances > 0.1 mass percentage","Technical UL/Output Current, Heavy-Duty Use (UL)":"625 A","Technical UL/Output Power, Light-Overload Use (UL)":"700 Hp","Technical UL/Output Current, Light-Overload Use (UL)":"807 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50000049062","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50000049062/alternatives.json"},"ai":{"faq":[{"question":"What is the SCIP number for this drive module?","answer":"The SCIP number is e9fd22a6-81c4-4079-87c1-83e8cf566d7a Finland, as registered under the EU waste framework directive."},{"question":"What are the key electrical ratings for this drive?","answer":"Normal-use: 450 kW, 820 A. Heavy-duty: 355 kW, 625 A. Light-overload: 450 kW, 810 A. Input is 380-480 V three-phase at 47.5-63 Hz. Apparent power output is 568 kVA."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50000049062","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50000049062 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}