{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50000049063","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50000049063","canonicalUrl":"https://aoctrl.com/abb/3AXD50000049063","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50000049063","rawCanonicalId":null},"summary":{"shortDescription":"ABB drive module, frame size R11, 500 kW normal-use output (880 A), 400 kW heavy-duty (725 A), 3-phase 380-480 V input, IP00, includes control unit.","salesMarkdown":"## What this drive module is and what it delivers The ABB 3AXD50000049063 is a drive module in frame size R11, delivering 500 kW normal-use output at 880 A, with a heavy-duty rating of 400 kW at 725 A. It runs on a 3-phase 380–480 V input and includes the control unit as standard. The module is rated for continuous duty at a maximum ambient temperature of 40 °C, with an altitude limit of 1000 m. It carries an IE2 efficiency level and a power factor of 0.98. Enclosure is IP00, NEMA Open Type, so it needs a cabinet for dust and touch protection. Standby loss sits at 615 W, and sound pressure is 71 dB(A) — worth factoring into panel cooling and noise budgets. ## I/O and communication — what is on board On the control side, the module provides 2 analog inputs, 2 analog outputs, and 6 digital inputs with 3 digital outputs. Communication is via CAN; there is no onboard industrial Ethernet interface. A lithium coin cell (CR2032, 220 mAh, 3 V) backs up the real-time clock and parameter storage. The battery is field-replaceable. ## Duty ratings — normal, heavy, light-overload Three duty classes are specified: normal use at 500 kW / 880 A, light-overload use at 500 kW / 865 A, and heavy-duty use at 400 kW / 725 A. The UL listing mirrors these: 700 Hp / 880 A normal, 500 Hp / 625 A heavy-duty. Normal-use 880 A suits variable-torque fans and pumps.","metaTitle":"ABB 3AXD50000049063 Drive Module, 500 kW, 880 A, Frame R11","metaDescription":"ABB 3AXD50000049063 drive module, 500 kW normal use, 880 A output, frame size R11. Current lifecycle stage. CAN interface, IP00, NEMA open type. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"SCIP":"e9fd22a6-81c4-4079-87c1-83e8cf566d7a Finland","Altitude":"1000 m","Includes":"Control unit","Frame Size":"R11","Power Factor":"0.98","Sound dB (A)":"71 dB(A)","Standby Loss":"615 W","Analog Inputs":"2","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Module","WEEE Category":"4. Large Equipment (Any External Dimension More Than 50 cm)","Analog Outputs":"2","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Temperature Rating":"Maximum 40 °C","Enclosure Type NEMA":"Open Type","Input Voltage (Uin)":"380 ... 480 V","Degree of Protection":"IP00","Apparent Power Output":"610 kV·A","Communication Protocol":"CAN","Power Consumption (@Pcons)":"10887 W","Operating Humidity (RHamβ)":"5 ... 95","Multiple Battery Information":"Lithium Coin, CR2032, 220 mAh, 3 V, 1 pc, 3 g","Number of Digital In/Outputs":"6 / 3","Number of Hardware Interfaces":"Industrial Ethernet 0","Output Power, Normal Use (Pn)":"500 kW","Output Current, Normal Use (In)":"880 A","Output Power, Heavy-Duty Use (PhD)":"400 kW","Output Current, Heavy-Duty Use (IhD)":"725 A","Output Power, Light-Overload Use (PlD)":"500 kW","Certificates and Declarations/RoHS Date":"20240508","Certificates and Declarations/REACH Date":"20250905","Output Current, Light-Overload Use (IlD)":"865 A","Technical UL/Output Power, Normal Use (UL)":"700 Hp","Technical UL/Output Current, Normal Use (UL)":"880 A","Certificates and Declarations/RoHS Information":"Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019","Technical UL/Output Power, Heavy-Duty Use (UL)":"500 Hp","Certificates and Declarations/REACH Information":"True - contains substances > 0.1 mass percentage","Technical UL/Output Current, Heavy-Duty Use (UL)":"625 A","Technical UL/Output Power, Light-Overload Use (UL)":"700 Hp","Technical UL/Output Current, Light-Overload Use (UL)":"807 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50000049063","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50000049063/alternatives.json"},"ai":{"faq":[{"question":"What are the key output ratings for this drive module?","answer":"Normal-use output is 500 kW at 880 A; heavy-duty is 400 kW at 725 A; light-overload is 500 kW at 865 A. UL normal-use is 700 Hp at 880 A, heavy-duty UL is 500 Hp at 625 A."},{"question":"What compliance documentation is available for this module?","answer":"RoHS compliant per EU Directive 2011/65/EU and 2015/863 (date 20240508). REACH declaration confirms substances >0.1% (date 20250905). SCIP number e9fd22a6-81c4-4079-87c1-83e8cf566d7a (Finland). UL listed for normal and heavy-duty use."},{"question":"What is the SCIP number for this product?","answer":"The SCIP number is e9fd22a6-81c4-4079-87c1-83e8cf566d7a, registered in Finland."},{"question":"What is the maximum operating altitude and ambient temperature?","answer":"Rated for a maximum altitude of 1000 m and a maximum ambient temperature of 40 °C."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50000049063","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50000049063 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}