{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50000049064","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50000049064","canonicalUrl":"https://aoctrl.com/abb/3AXD50000049064","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50000049064","rawCanonicalId":null},"summary":{"shortDescription":"ABB drive module, R10 frame, 250 kW / 505 A normal-use output, 380-480 VAC 3-phase, IP00, BACnet, RoHS/REACH compliant.","salesMarkdown":"## Drive module, R10 frame — 250 kW normal-use, 505 A continuous The ABB 3AXD50000049064 is a 3-phase drive module in an R10 frame, delivering 250 kW normal-use output power at 505 A continuous current. Heavy-duty use is rated 200 kW / 361 A, light-overload use 250 kW / 485 A. Apparent power output is 350 kV·A. Input voltage range is 380…480 VAC, 47.5…63 Hz. Ambient temperature limit is 40 °C; altitude rating is 1000 m. Enclosure is IP00 open type, so panel integration requires additional protection against dust and contact. ## Integration notes Mounts as a module — no enclosure included. Standby loss is 423 W; power consumption at full load is 6492 W. Sound level is 72 dB(A). Includes a control unit. Analog I/O: 2 inputs, 2 outputs. Digital I/O: 6 inputs, 3 outputs. Communication is BACnet; no Industrial Ethernet interface on this variant. A lithium coin cell (CR2032, 220 mAh, 3 V) is fitted for backup. Operating humidity up to 95% RH non-condensing. Efficiency class IE2.","metaTitle":"ABB 3AXD50000049064 Drive Module, 250 kW, 505 A, R10 Frame","metaDescription":"ABB drive module, 250 kW normal-use output, 505 A, 380-480 VAC, 3-phase. R10 frame, IP00, BACnet, RoHS/REACH compliant. Current lifecycle stage. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"SCIP":"58f22844-2faf-42d0-845e-c7388e32f3e4 Finland","title":"3AXD50000049064","Altitude":"1000 m","Includes":"Control unit","Frame Size":"R10","description":"LV AC drive module for HVAC, IEC: Pn 250 kW, 505 A, 400 V, UL: Pld 400 Hp, 483 A, 480 V (ACH580-04-505A-4)","Sound dB (A)":"72 dB(A)","Standby Loss":"423 W","Analog Inputs":"2","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Module","WEEE Category":"4. Large Equipment (Any External Dimension More Than 50 cm)","Analog Outputs":"2","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Temperature Rating":"Maximum 40 °C","Enclosure Type NEMA":"Open Type","Input Voltage (Uin)":"380 ... 480 V","Degree of Protection":"IP00","Apparent Power Output":"350 kV·A","Communication Protocol":"BACNET","Power Consumption (@Pcons)":"6492 W","Operating Humidity (RHamβ)":"95","Multiple Battery Information":"Lithium Coin, CR2032, 220 mAh, 3 V, 1 pc, 3 g","Number of Digital In/Outputs":"6 / 3","Number of Hardware Interfaces":"Industrial Ethernet 0","Output Power, Normal Use (Pn)":"250 kW","Output Current, Normal Use (In)":"505 A","Output Power, Heavy-Duty Use (PhD)":"200 kW","Output Current, Heavy-Duty Use (IhD)":"361 A","Output Power, Light-Overload Use (PlD)":"250 kW","Certificates and Declarations/RoHS Date":"20240508","Certificates and Declarations/REACH Date":"20250905","Output Current, Light-Overload Use (IlD)":"485 A","Technical UL/Output Current, Normal Use (UL)":"505 A","Certificates and Declarations/RoHS Information":"Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019","Technical UL/Output Power, Heavy-Duty Use (UL)":"300 Hp","Certificates and Declarations/REACH Information":"True - contains substances > 0.1 mass percentage","Technical UL/Output Current, Heavy-Duty Use (UL)":"361 A","Technical UL/Output Power, Light-Overload Use (UL)":"400 Hp","Technical UL/Output Current, Light-Overload Use (UL)":"483 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/0b1b2f25204a4199ca16bd37adaff37c.pdf","sourceUrl":"https://www.abb.com/global/en/products/3axd50000049064"},"ai":{"faq":[{"question":"What are the key output ratings for this drive module?","answer":"Normal-use output is 250 kW at 505 A; heavy-duty use is 200 kW at 361 A; light-overload use is 250 kW at 485 A. Apparent power is 350 kV·A."},{"question":"What compliance documentation is available for the 3AXD50000049064?","answer":"RoHS compliant per EU Directive 2011/65/EU and Amendment 2015/863. REACH declaration confirms substances above 0.1 mass percentage. SCIP number is 58f22844-2faf-42d0-845e-c7388e32f3e4 Finland."},{"question":"What is the enclosure type and ambient temperature limit?","answer":"IP00 open type — no ingress protection, so it must be installed inside a suitable cabinet. Maximum ambient temperature is 40 °C."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50000049064","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50000049064 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}