{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50000049065","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50000049065","canonicalUrl":"https://aoctrl.com/abb/3AXD50000049065","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50000049065","rawCanonicalId":null},"summary":{"shortDescription":"ABB, drive module, 3AXD50000049065, R10 frame, 315 kW normal use / 585 A, 250 kW heavy duty / 429 A, BACnet, IP00, IE2.","salesMarkdown":"## Drive module for 380–480 V three-phase systems The ABB 3AXD50000049065 is a drive module on an R10 frame, rated for 315 kW normal use (585 A output) and 250 kW heavy-duty use (429 A output) from a 380–480 V three-phase supply. It includes the control unit and communicates via BACnet. This module carries three duty ratings that map to different application profiles. Heavy-duty use (PhD 250 kW, IhD 429 A) applies to constant-torque or high-starting-torque applications such as conveyors or extruders. Light-overload use (PlD 315 kW, IlD 575 A) covers intermittent overloads above the normal rating. The UL listing confirms the same currents: 585 A normal, 414 A heavy duty (350 Hp), and 573 A light overload (450 Hp). ## Integration notes Mounts as a module; the R10 frame determines the physical footprint and bus bar connections. Ambient temperature must not exceed 40 °C, and installation altitude is limited to 1000 m without derating. Standby loss is 423 W, and full-load power consumption is 6840 W. The control unit includes 2 analog inputs, 2 analog outputs, 6 digital inputs, and 3 digital outputs. There is no onboard industrial Ethernet interface — BACnet is the communication protocol. A lithium coin cell (CR2032, 220 mAh, 3 V) backs the real-time clock. Sound level is 72 dB(A).","metaTitle":"ABB 3AXD50000049065 Drive Module, R10, 315 kW, 585 A","metaDescription":"ABB 3AXD50000049065 drive module, R10 frame, 315 kW normal use (585 A), 250 kW heavy duty (429 A). BACnet, IP00, IE2. Current lifecycle stage. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"SCIP":"58f22844-2faf-42d0-845e-c7388e32f3e4 Finland","title":"3AXD50000049065","Altitude":"1000 m","Includes":"Control unit","Frame Size":"R10","description":"LV AC drive module for HVAC, IEC: Pn 315 kW, 585 A, 400 V, UL: Pld 450 Hp, 573 A, 480 V (ACH580-04-585A-4)","Sound dB (A)":"72 dB(A)","Standby Loss":"423 W","Analog Inputs":"2","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Module","WEEE Category":"4. Large Equipment (Any External Dimension More Than 50 cm)","Analog Outputs":"2","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Temperature Rating":"Maximum 40 °C","Enclosure Type NEMA":"Open Type","Input Voltage (Uin)":"380 ... 480 V","Degree of Protection":"IP00","Apparent Power Output":"405 kV·A","Communication Protocol":"BACNET","Power Consumption (@Pcons)":"6840 W","Operating Humidity (RHamβ)":"95","Multiple Battery Information":"Lithium Coin, CR2032, 220 mAh, 3 V, 1 pc, 3 g","Number of Digital In/Outputs":"6 / 3","Number of Hardware Interfaces":"Industrial Ethernet 0","Output Power, Normal Use (Pn)":"315 kW","Output Current, Normal Use (In)":"585 A","Output Power, Heavy-Duty Use (PhD)":"250 kW","Output Current, Heavy-Duty Use (IhD)":"429 A","Output Power, Light-Overload Use (PlD)":"315 kW","Certificates and Declarations/RoHS Date":"20240508","Certificates and Declarations/REACH Date":"20250905","Output Current, Light-Overload Use (IlD)":"575 A","Technical UL/Output Current, Normal Use (UL)":"585 A","Certificates and Declarations/RoHS Information":"Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019","Technical UL/Output Power, Heavy-Duty Use (UL)":"350 Hp","Certificates and Declarations/REACH Information":"True - contains substances > 0.1 mass percentage","Technical UL/Output Current, Heavy-Duty Use (UL)":"414 A","Technical UL/Output Power, Light-Overload Use (UL)":"450 Hp","Technical UL/Output Current, Light-Overload Use (UL)":"573 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/f7491b3242a31569f13e8ae7a9e232b2.pdf","sourceUrl":"https://www.abb.com/global/en/products/3axd50000049065"},"ai":{"faq":[{"question":"What are the key ratings for this drive module?","answer":"Normal use: 315 kW, 585 A. Heavy-duty use: 250 kW, 429 A. Light-overload use: 315 kW, 575 A. Input is 380–480 V three-phase."},{"question":"What compliance documentation is available?","answer":"RoHS per EU Directive 2011/65/EU and Amendment 2015/863, REACH declaration (substances > 0.1% present), and UL listing for normal/heavy-duty/light-overload currents and horsepower."},{"question":"What communication protocol does this module use?","answer":"BACnet. There is no onboard industrial Ethernet interface."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50000049065","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50000049065 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}