{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50000050414","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50000050414","canonicalUrl":"https://aoctrl.com/abb/3AXD50000050414","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50000050414","rawCanonicalId":null},"summary":{"shortDescription":"ABB, ACS880-17 series, regenerative drive, 3AXD50000050414, 250 kW, 271 A, 525-690 V, 3-phase, frame R11, IP22.","salesMarkdown":"## Drive ratings and duty selection The ABB 3AXD50000050414 is an ACS880-17-0271A-7 regenerative drive rated 250 kW normal-use output (271 A) on a 525-690 V three-phase supply. Light-overload use (250 kW, 257 A) mirrors the normal-use power but with a slightly lower current — relevant when the load profile is mostly centrifugal. Frame size R11 and IP22 enclosure mean this drive is built for cabinet mounting in a controlled environment. The 77 dB(A) sound level is worth noting for panel placement near operator stations — not a quiet unit. Ambient temperature is capped at 40 °C, with derating needed above that; altitude is rated to 1000 m without further derating. ## Regenerative drive — ecodesign exemption This regenerative drive is exempt from EU ecodesign efficiency requirements under Regulation EU/2019/1781 §2.3.c. The SCIP number is 82D82DAE-9725-4373-865D-AA949B97DE50 Finland for EU substance reporting. The control unit includes 2 analog inputs, 2 analog outputs, 7 digital inputs, and 5 digital outputs. Communication is via CAN; there is no onboard Industrial Ethernet interface. The battery information lists two CR2032 lithium coin cells (3 V, 220 mAh each) for real-time-clock backup — factor those into preventive maintenance schedules.","metaTitle":"ABB 3AXD50000050414 ACS880-17 Drive, 250 kW, 271 A","metaDescription":"ABB ACS880-17-0271A-7 drive, 250 kW normal use, 271 A output, 525-690 V input, frame R11, IP22. Active lifecycle, sourced to order. SCIP: 82D82DAE-9725-4373-865D-AA949B97DE50 Finla","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 600V"],"specifications":{"SCIP":"82D82DAE-9725-4373-865D-AA949B97DE50 Finland","Altitude":"1000 m","Includes":"Control unit","Frame Size":"R11","Power Factor":"1","Sound dB (A)":"77 dB(A)","Analog Inputs":"2","Frequency (f)":"48 ... 63 Hz","WEEE Category":"4. Large Equipment (Any External Dimension More Than 50 cm)","Analog Outputs":"2","lifecycle_stage":"current","Number of Phases":"3-phase","Temperature Rating":"Maximum 40 °C","Ecodesign Exemption":"Energy efficiency data is not provided for the drive. The regenerative drives are exempt from the EU ecodesign requirements (Regulation EU/2019/1781, §2.3.c).","Enclosure Type NEMA":"Type1","Input Voltage (Uin)":"525 ... 690 V","Degree of Protection":"IP22","Apparent Power Output":"324 kV·A","Communication Protocol":"CAN","Operating Humidity (RHamβ)":"5 ... 95","Multiple Battery Information":"Lithium Coin, CR2032, 2pcs, 3V, 220mAh, 6g","Number of Digital In/Outputs":"7 / 5","Number of Hardware Interfaces":"Industrial Ethernet 0","Output Power, Normal Use (Pn)":"250 kW","Output Current, Normal Use (In)":"271 A","Output Power, Heavy-Duty Use (PhD)":"200 kW","Output Current, Heavy-Duty Use (IhD)":"210 A","Output Power, Light-Overload Use (PlD)":"250 kW","Output Current, Light-Overload Use (IlD)":"257 A","Technical UL/Output Power, Normal Use (UL)":"- Hp","Technical UL/Output Current, Normal Use (UL)":"- A","Technical UL/Output Power, Heavy-Duty Use (UL)":"200 Hp","Technical UL/Output Current, Heavy-Duty Use (UL)":"210 A","Technical UL/Output Power, Light-Overload Use (UL)":"250 Hp","Technical UL/Output Current, Light-Overload Use (UL)":"257 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50000050414","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50000050414/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings for this drive?","answer":"Normal-use output is 250 kW at 271 A; heavy-duty use is 200 kW at 210 A. Input voltage range is 525-690 V three-phase. Frame size is R11 with IP22 protection."},{"question":"What is the SCIP number for this product?","answer":"The SCIP number is 82D82DAE-9725-4373-865D-AA949B97DE50 Finland, as listed for EU substance compliance reporting."},{"question":"Does this drive have an efficiency rating?","answer":"No. As a regenerative drive, it is exempt from EU ecodesign requirements (Regulation EU/2019/1781, §2.3.c), so no IE-class efficiency data is provided."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50000050414","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50000050414 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}