{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50000050474","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50000050474","canonicalUrl":"https://aoctrl.com/abb/3AXD50000050474","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50000050474","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACH580-07 LV AC cabinet-built drive, 3AXD50000050474, 450 kW / 820 A normal duty, 355 kW / 625 A heavy duty, 380-480 V, IP21, Type 1, frame R11.","salesMarkdown":"The ABB 3AXD50000050474 is the order code for a cabinet-built LV AC drive, frame size R11, rated 450 kW normal-duty output at 820 A and 355 kW heavy-duty at 625 A on a 400 V supply. It ships with the control unit included and is configured for 3-phase input at 380...480 V, 47.5...63 Hz. The IP21 / NEMA Type 1 enclosure suits indoor installation in HVAC plant rooms or light industrial environments. Normal-duty current of 820 A covers centrifugal pumps and fans with constant torque profiles. The UL listing shows 500 Hp heavy-duty and 700 Hp light-overload, so the drive is dual-rated for North American and IEC specs. ## Integration notes The drive includes 2 analog inputs, 2 analog outputs, and 6 digital inputs / 3 digital outputs. BACnet is the listed communication protocol, which aligns with HVAC building management integration. No industrial Ethernet interface is onboard — BACnet MS/TP over RS-485 is the primary fieldbus. The control unit is included in the delivery; no separate ordering needed. Cabinet-built means the drive arrives as a self-contained assembly with power section, control, and auxiliaries wired. The R11 frame is large — expect a floor-standing cabinet, not a wall-mount. Sound level is rated at 72 dB(A), so plan for acoustic isolation if installed near occupied spaces. Ambient temperature limit is 40 °C maximum; derate above that. Operating humidity range is 5 to 95% non-condensing. ## Compliance documentation The drive carries a lithium coin cell (CR2032, 220 mAh, 3 V) for real-time clock backup. WEEE category 4 (Large Equipment) applies for end-of-life take-back. Ecodesign energy efficiency data is not provided because cabinet-built drives with conform modules are excluded from EU 2019/1781 scope per §2.3.e.","metaTitle":"ABB 3AXD50000050474 ACH580-07 Cabinet Drive, 450 kW","metaDescription":"ABB ACH580-07 cabinet-built drive, 450 kW / 820 A normal duty, 355 kW / 625 A heavy duty. Active production. RoHS/REACH compliant. SCIP registered. RFQ for lead time.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"SCIP":"2361a3f3-2fee-41b4-bbdb-00925564e194 Finland","title":"3AXD50000050474","Includes":"Control unit","Frame Size":"R11","description":"LV AC cabinet-built drive for HVAC, IEC: Pn 450 kW, 820 A, 400 V, UL: Pld 700 Hp, 807 A, 480 V (ACH580-07-0820A-4)","Sound dB (A)":"72 dB(A)","Analog Inputs":"2","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Cabinet-built","WEEE Category":"4. Large Equipment (Any External Dimension More Than 50 cm)","Analog Outputs":"2","lifecycle_stage":"current","Number of Phases":"3-phase","Temperature Rating":"Maximum 40 °C","Ecodesign Exemption":"Energy efficiency data is not provided for this cabinet-based drive. Cabinet built drives, with already conform modules, are excluded from the scope of the EU ecodesign requirements (Regulation EU/2019/1781, §2.3.e).","Enclosure Type NEMA":"Type1","Input Voltage (Uin)":"380 ... 480 V","Degree of Protection":"IP21","Apparent Power Output":"568 kV·A","Communication Protocol":"BACNET","Power Consumption (@Pcons)":"13725 W","Operating Humidity (RHamβ)":"5 to 95%","Multiple Battery Information":"Lithium Coin, CR2032, 220 mAh, 3 V, 1 pc, 3 g","Number of Digital In/Outputs":"6 / 3","Number of Hardware Interfaces":"Industrial Ethernet 0","Output Power, Normal Use (Pn)":"450 kW","Output Current, Normal Use (In)":"820 A","Output Power, Heavy-Duty Use (PhD)":"355 kW","Output Current, Heavy-Duty Use (IhD)":"625 A","Output Power, Light-Overload Use (PlD)":"450 kW","Certificates and Declarations/RoHS Date":"20240508","Certificates and Declarations/REACH Date":"20250905","Output Current, Light-Overload Use (IlD)":"810 A","Certificates and Declarations/RoHS Information":"Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019","Technical UL/Output Power, Heavy-Duty Use (UL)":"500 Hp","Certificates and Declarations/REACH Information":"True - contains substances > 0.1 mass percentage","Technical UL/Output Current, Heavy-Duty Use (UL)":"625 A","Technical UL/Output Power, Light-Overload Use (UL)":"700 Hp","Technical UL/Output Current, Light-Overload Use (UL)":"807 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/9d47ac4c1b0557a1ed1ba912b9e7ed8d.pdf","sourceUrl":"https://www.abb.com/global/en/products/3axd50000050474"},"ai":{"faq":[{"question":"What is the SCIP number for this drive?","answer":"The SCIP number is 2361a3f3-2fee-41b4-bbdb-00925564e194 Finland."},{"question":"Does the drive include the control unit?","answer":"Yes, the control unit is included with the order code 3AXD50000050474."},{"question":"What are the key ratings for normal and heavy duty?","answer":"Normal-duty output is 450 kW / 820 A; heavy-duty output is 355 kW / 625 A. Light-overload output is 450 kW / 810 A. UL ratings are 700 Hp / 807 A light-overload and 500 Hp / 625 A heavy-duty."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50000050474","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50000050474 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}