{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50000050481","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50000050481","canonicalUrl":"https://aoctrl.com/abb/3AXD50000050481","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50000050481","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACQ580-07 LV AC cabinet-built drive, 3AXD50000050481, 500 kW, 880 A, 400 V, IP21, NEMA 1, frame R11.","salesMarkdown":"## Drive selection note for the 3AXD50000050481 LV AC cabinet-built drive sized for a 500 kW normal-use induction motor at 880 A output on a 400 V three-phase supply. Heavy-duty use derates to 400 kW and 725 A; light-overload use holds the 500 kW but draws 865 A. ## What the duty ratings mean for pump and fan loads The normal-use (Pn) rating of 500 kW / 880 A is the curve for variable-torque loads — pumps and fans with quadratic torque-speed profiles. The 0.98 power factor reflects the active front-end or integrated filter; expect near-unity PF across the operating band. Sound level is 71 dB(A) — typical for an R11 frame at full load; plan for panel-door attenuation if the drive is in a quiet zone. ## I/O and communication at a glance Two analog inputs and two analog outputs are onboard. Digital I/O counts 6 inputs and 3 outputs. Communication is CAN-based; there are zero Industrial Ethernet interfaces on this variant. Ambient temperature limit is 40 °C maximum; operating humidity spans 5 to 95 % RH. The drive includes a CR2032 lithium coin cell for real-time clock backup — 220 mAh, 3 V, 1 piece, 3 g.","metaTitle":"ABB 3AXD50000050481 ACQ580-07 Cabinet Drive, 500 kW, 880 A","metaDescription":"ABB ACQ580-07 LV AC cabinet-built drive, 500 kW / 880 A normal use, 400 V, IP21, NEMA 1. Current lifecycle stage. SCIP registered. RoHS/REACH compliant. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"SCIP":"2361a3f3-2fee-41b4-bbdb-00925564e194 Finland","Includes":"Control unit","Frame Size":"R11","Power Factor":"0.98","Sound dB (A)":"71 dB(A)","Analog Inputs":"2","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Cabinet-built","WEEE Category":"4. Large Equipment (Any External Dimension More Than 50 cm)","Analog Outputs":"2","lifecycle_stage":"current","Number of Phases":"3-phase","Temperature Rating":"Maximum 40 °C","Ecodesign Exemption":"Energy efficiency data is not provided for this cabinet-based drive. Cabinet built drives, with already conform modules, are excluded from the scope of the EU ecodesign requirements (Regulation EU/2019/1781, §2.3.e).","Enclosure Type NEMA":"Type1","Input Voltage (Uin)":"380 ... 480 V","Degree of Protection":"IP21","Apparent Power Output":"610 kV·A","Communication Protocol":"CAN","Power Consumption (@Pcons)":"15300 W","Operating Humidity (RHamβ)":"5 ... 95","Multiple Battery Information":"Lithium Coin, CR2032, 220 mAh, 3 V, 1 pc, 3 g","Number of Digital In/Outputs":"6 / 3","Number of Hardware Interfaces":"Industrial Ethernet 0","Output Power, Normal Use (Pn)":"500 kW","Output Current, Normal Use (In)":"880 A","Output Power, Heavy-Duty Use (PhD)":"400 kW","Output Current, Heavy-Duty Use (IhD)":"725 A","Output Power, Light-Overload Use (PlD)":"500 kW","Certificates and Declarations/RoHS Date":"20240508","Certificates and Declarations/REACH Date":"20250905","Output Current, Light-Overload Use (IlD)":"865 A","Certificates and Declarations/RoHS Information":"Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019","Technical UL/Output Power, Heavy-Duty Use (UL)":"500 Hp","Certificates and Declarations/REACH Information":"True - contains substances > 0.1 mass percentage","Technical UL/Output Current, Heavy-Duty Use (UL)":"625 A","Technical UL/Output Power, Light-Overload Use (UL)":"700 Hp","Technical UL/Output Current, Light-Overload Use (UL)":"807 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50000050481","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50000050481/alternatives.json"},"ai":{"faq":[{"question":"What is the SCIP number for this drive?","answer":"SCIP number 2361a3f3-2fee-41b4-bbdb-00925564e194 (Finland)."},{"question":"What compliance documentation does ABB provide for the 3AXD50000050481?","answer":"RoHS compliance per EU Directive 2011/65/EU and Amendment 2015/863 (RoHS date 20240508), REACH declaration with substances > 0.1 mass percentage (REACH date 20250905), and an ecodesign exemption for cabinet-built drives under EU/2019/1781 §2.3.e."},{"question":"What are the key ratings for the 3AXD50000050481?","answer":"Normal-use output 500 kW / 880 A, heavy-duty 400 kW / 725 A, light-overload 500 kW / 865 A. Input 380–480 V three-phase, 47.5–63 Hz. Apparent power 610 kVA. UL heavy-duty 500 Hp / 625 A, UL light-overload 700 Hp / 807 A."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50000050481","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50000050481 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}