{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50000121106","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50000121106","canonicalUrl":"https://aoctrl.com/abb/3AXD50000121106","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50000121106","rawCanonicalId":null},"summary":{"shortDescription":"ABB 3AXD50000121106, R6 frame drive, 380-500 VAC 3-phase input, 52 A normal-duty / 40 A heavy-duty output, IP21, wall-mounted, CAN interface.","salesMarkdown":"The ABB 3AXD50000121106 is a current-production, R6-frame drive rated for 380 to 500 VAC three-phase input. It delivers 52 A in normal-duty use (30 kW) and 40 A in heavy-duty use (22 kW), with a light-overload rating of 49 A (30 kW). The enclosure is IP21, wall-mounted, and includes the control unit. This drive communicates via CAN — there are no industrial Ethernet ports on board. It carries 2 analog inputs, 2 analog outputs, and 6 digital inputs plus 2 digital outputs. That's enough I/O for basic standalone control or a CAN-based machine network, but if you need PROFINET or EtherNet/IP, you'll be adding an option module. ## Sourcing posture This is an active, current-production drive.","metaTitle":"ABB 3AXD50000121106 Drive, R6, 52A Normal, 40A Heavy Duty","metaDescription":"ABB 3AXD50000121106 drive, frame R6, 380-500V 3-phase input, 52A normal / 40A heavy-duty output, IP21, wall-mounted, CAN. Active production, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Inverter / VFD"],"specifications":{"SCIP":"9350477b-4019-4321-ae55-edeae10d256e Finland","Altitude":"4000 m","Includes":"Control unit","Frame Size":"R6","Power Factor":"1.0","Sound dB (A)":"71 dB(A)","Standby Loss":"55 W","Analog Inputs":"2","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Wall-mounted","WEEE Category":"4. Large Equipment (Any External Dimension More Than 50 cm)","Analog Outputs":"2","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Temperature Rating":"Maximum +55 °C","Ecodesign Exemption":"Energy efficiency data is not provided for the drive. The low-harmonic drives are exempt from the EU ecodesign requirements (Regulation EU/2019/1781, §2.3.d).","Enclosure Type NEMA":"Type1","Input Voltage (Uin)":"380 ... 500 V","Degree of Protection":"IP21","Apparent Power Output":"45 kV·A","Communication Protocol":"CAN","Power Consumption (@Pcons)":"885 W","Operating Humidity (RHamβ)":"5 ... 95","Multiple Battery Information":"Lithium Coin, CR2032, 220 mAh, 3 V, 2 pcs, 6 g","Number of Digital In/Outputs":"6 / 2","Number of Hardware Interfaces":"Industrial Ethernet 0","Output Power, Normal Use (Pn)":"30 kW","Output Current, Normal Use (In)":"52 A","Output Power, Heavy-Duty Use (PhD)":"22.0 kW","Output Current, Heavy-Duty Use (IhD)":"40 A","Output Power, Light-Overload Use (PlD)":"30.0 kW","Certificates and Declarations/RoHS Date":"20240508","Certificates and Declarations/REACH Date":"20250905","Output Current, Light-Overload Use (IlD)":"49 A","Certificates and Declarations/RoHS Information":"Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019","Technical UL/Output Power, Heavy-Duty Use (UL)":"30.0 Hp","Certificates and Declarations/REACH Information":"True - contains substances > 0.1 mass percentage","Technical UL/Output Current, Heavy-Duty Use (UL)":"40.0 A","Technical UL/Output Power, Light-Overload Use (UL)":"40 Hp","Technical UL/Output Current, Light-Overload Use (UL)":"52 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50000121106","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50000121106/alternatives.json"},"ai":{"faq":[{"question":"What is the SCIP number for this drive?","answer":"The SCIP number is 9350477b-4019-4321-ae55-edeae10d256e, registered in Finland."},{"question":"What compliance documentation is available?","answer":"RoHS compliance per EU Directive 2011/65/EU (date 20240508) and REACH registration (date 20250905) with a substance declaration above 0.1% mass. UL ratings are also listed for heavy-duty and light-overload use."},{"question":"What is the maximum operating altitude?","answer":"4000 m without derating."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50000121106","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50000121106 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}