{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50000121267","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50000121267","canonicalUrl":"https://aoctrl.com/abb/3AXD50000121267","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50000121267","rawCanonicalId":null},"summary":{"shortDescription":"ABB drive, R8 frame, 3-phase, 380–500 V input, 90 kW / 156 A normal-duty output, IP21, wall-mounted.","salesMarkdown":"The ABB 3AXD50000121267 is a current-production R8-frame drive rated for 90 kW normal-duty output at 156 A on a 380–500 V three-phase supply. Heavy-duty use drops to 75.0 kW / 124 A; light-overload use holds at 90.0 kW / 148 A. UL listing matches the heavy-duty current at 124 A and rates the light-overload output at 125 Hp. Wall-mounted with an IP21 / NEMA Type 1 enclosure, it handles ambient temperatures up to +55 °C and altitudes to 4000 m. Standby loss is 89 W; full-load power consumption runs 2766 W at the listed apparent power of 135 kV·A. Onboard I/O includes 2 analog inputs, 2 analog outputs, and 6 digital inputs plus 2 digital outputs. Communication is CAN-based; no onboard Industrial Ethernet port. A CR2032 lithium coin cell (2 pcs, 220 mAh each) backs the real-time clock.","metaTitle":"ABB 3AXD50000121267 Drive, R8 Frame, 90 kW, 156 A","metaDescription":"ABB 3AXD50000121267 drive, R8 frame, 90 kW normal-duty output at 156 A. IP21, Type 1, wall-mount. Current production. RoHS/REACH/UL compliant. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Inverter / VFD"],"specifications":{"SCIP":"15292056-d176-4797-82ee-344739f8f7bc Finland","Altitude":"4000 m","Includes":"Control unit","Frame Size":"R8","Power Factor":"1.0","Sound dB (A)":"68 dB(A)","Standby Loss":"89 W","Analog Inputs":"2","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Wall-mounted","WEEE Category":"4. Large Equipment (Any External Dimension More Than 50 cm)","Analog Outputs":"2","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Temperature Rating":"Maximum +55 °C","Ecodesign Exemption":"Energy efficiency data is not provided for the drive. The low-harmonic drives are exempt from the EU ecodesign requirements (Regulation EU/2019/1781, §2.3.d).","Enclosure Type NEMA":"Type1","Input Voltage (Uin)":"380 ... 500 V","Degree of Protection":"IP21","Apparent Power Output":"135 kV·A","Communication Protocol":"CAN","Power Consumption (@Pcons)":"2766 W","Operating Humidity (RHamβ)":"5 ... 95","Multiple Battery Information":"Lithium Coin, CR2032, 220 mAh, 3 V, 2 pcs, 6 g","Number of Digital In/Outputs":"6 / 2","Number of Hardware Interfaces":"Industrial Ethernet 0","Output Power, Normal Use (Pn)":"90 kW","Output Current, Normal Use (In)":"156 A","Output Power, Heavy-Duty Use (PhD)":"75.0 kW","Output Current, Heavy-Duty Use (IhD)":"124 A","Output Power, Light-Overload Use (PlD)":"90.0 kW","Certificates and Declarations/RoHS Date":"20240508","Certificates and Declarations/REACH Date":"20250905","Output Current, Light-Overload Use (IlD)":"148 A","Certificates and Declarations/RoHS Information":"Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019","Technical UL/Output Power, Heavy-Duty Use (UL)":"100.0 Hp","Certificates and Declarations/REACH Information":"True - contains substances > 0.1 mass percentage","Technical UL/Output Current, Heavy-Duty Use (UL)":"124.0 A","Technical UL/Output Power, Light-Overload Use (UL)":"125 Hp","Technical UL/Output Current, Light-Overload Use (UL)":"156 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50000121267","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50000121267/alternatives.json"},"ai":{"faq":[{"question":"What is the SCIP number for this drive?","answer":"SCIP 15292056-d176-4797-82ee-344739f8f7bc Finland."},{"question":"What are the key output ratings?","answer":"Normal duty: 90 kW / 156 A. Heavy duty: 75.0 kW / 124 A. Light overload: 90.0 kW / 148 A. UL heavy-duty: 100 Hp / 124 A; UL light-overload: 125 Hp."},{"question":"What is the maximum altitude rating?","answer":"4000 m."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50000121267","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50000121267 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}