{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50000136797","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50000136797","canonicalUrl":"https://aoctrl.com/abb/3AXD50000136797","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50000136797","rawCanonicalId":null},"summary":{"shortDescription":"ABB drive module, frame size R1, 1.5 kW normal-use output at 7.8 A, 200–240 V 3-phase, IP20, CAN interface.","salesMarkdown":"## Output ratings and duty selection The 3AXD50000136797: Three duty ratings are specified: normal use (Pn 1.5 kW, In 7.8 A), heavy-duty use (PhD 1.1 kW, IhD 6.9 A), and light-overload use (PlD 1.5 kW, IlD 7.5 A). The heavy-duty figure governs continuous operation under high starting torque or cyclic loads; the normal and light-overload figures are for lower-duty profiles. UL listings match: heavy-duty 1.5 Hp / 6.6 A, light-overload 2 Hp / 7.5 A. ## Supply and environmental limits Input is 200–240 V three-phase, 47.5–63 Hz. Ambient temperature maximum 50 °C, operating humidity 5–95 % RH non-condensing, altitude up to 1000 m without derating. Enclosure is IP20 open type (NEMA Open Type). Standby loss is 15 W; full-load power consumption is 105 W. Apparent power output is 3.1 kV·A. Sound level 63.1 dB(A). Digital I/O: 2 inputs, 1 output. No analog I/O. Communication is via CAN; no industrial Ethernet interface on this module.","metaTitle":"ABB 3AXD50000136797 Drive Module, R1 Frame, 1.5 kW Normal","metaDescription":"ABB drive module, frame size R1, 1.5 kW normal-use output (7.8 A) on 200–240 V 3-phase. Active lifecycle. SCIP 483516f7-5042-4d76-a918-d7fab20a54ce Finland. RoHS/REACH compliant. S","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 240V"],"specifications":{"SCIP":"483516f7-5042-4d76-a918-d7fab20a54ce Finland","Altitude":"1000 m","Includes":"Control unit","Frame Size":"R1","Power Factor":"0.98","Sound dB (A)":"63.10 dB(A)","Standby Loss":"15 W","Analog Inputs":"0","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Module","WEEE Category":"5. Small Equipment (No External Dimension More Than 50 cm)","Analog Outputs":"0","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Temperature Rating":"Maximum 50 °C","Enclosure Type NEMA":"Open Type","Input Voltage (Uin)":"200 ... 240 V","Degree of Protection":"IP20","Apparent Power Output":"3.1 kV·A","Communication Protocol":"CAN","Power Consumption (@Pcons)":"105 W","Operating Humidity (RHamβ)":"5 ... 95","Multiple Battery Information":"No battery / cell included","Number of Digital In/Outputs":"2 / 1","Number of Hardware Interfaces":"Industrial Ethernet 0","Output Power, Normal Use (Pn)":"1.5 kW","Output Current, Normal Use (In)":"7.8 A","Output Power, Heavy-Duty Use (PhD)":"1.1 kW","Output Current, Heavy-Duty Use (IhD)":"6.9 A","Output Power, Light-Overload Use (PlD)":"1.5 kW","Certificates and Declarations/RoHS Date":"20230303","Certificates and Declarations/REACH Date":"20250905","Output Current, Light-Overload Use (IlD)":"7.5 A","Certificates and Declarations/RoHS Information":"Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019","Technical UL/Output Power, Heavy-Duty Use (UL)":"1.5 Hp","Certificates and Declarations/REACH Information":"True - contains substances > 0.1 mass percentage","Technical UL/Output Current, Heavy-Duty Use (UL)":"6.6 A","Technical UL/Output Power, Light-Overload Use (UL)":"2 Hp","Technical UL/Output Current, Light-Overload Use (UL)":"7.5 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50000136797","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50000136797/alternatives.json"},"ai":{"faq":[{"question":"What are the output ratings for normal, heavy-duty, and light-overload use?","answer":"Normal use: 1.5 kW / 7.8 A. Heavy-duty use: 1.1 kW / 6.9 A. Light-overload use: 1.5 kW / 7.5 A. UL heavy-duty: 1.5 Hp / 6.6 A; UL light-overload: 2 Hp / 7.5 A."},{"question":"What compliance documentation is available for this drive module?","answer":"RoHS compliant per EU Directive 2011/65/EU and Amendment 2015/863 (date 20230303). REACH declaration confirms substances above 0.1 mass percentage (date 20250905). SCIP number 483516f7-5042-4d76-a918-d7fab20a54ce Finland is on file."},{"question":"What is the input voltage and phase requirement?","answer":"200–240 V three-phase, 47.5–63 Hz."},{"question":"What is the frame size and enclosure rating?","answer":"Frame size R1. Enclosure is IP20, NEMA Open Type."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50000136797","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50000136797 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}