{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50000145829","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50000145829","canonicalUrl":"https://aoctrl.com/abb/3AXD50000145829","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50000145829","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACS880-17 regenerative drive, 3AXD50000145829, 710 kW / 1010 A normal use, 500 kW heavy-duty, 380-500 VAC 3-phase, IP22, Type 1, active production.","salesMarkdown":"## Duty ratings — normal, heavy, light overload The 3AXD50000145829: Three duty curves are listed. Normal use (Pn) delivers 710 kW / 1010 A; heavy-duty (PhD) drops to 500 kW / 755 A for constant-torque loads like conveyors or extruders; light-overload (PlD) sits at 630 kW / 970 A. The UL column mirrors these: 900 Hp normal, 600 Hp heavy, 800 Hp light. If your application is a pump or fan with variable torque, the normal-use figure is your sizing target. For a crusher or press, size against the heavy-duty line. ## Enclosure, protection, and environment IP22 with NEMA Type 1 — suitable for indoor, dry locations where a finger probe is the main concern, not dust or hose-down. Maximum ambient 40 °C, altitude 1000 m without derating. Operating humidity 5–95% non-condensing. Sound pressure at 77 dB(A) — noticeable in a quiet control room; ear protection not mandatory but the hum is there. Four analog inputs, four analog outputs, 14 digital inputs / 10 digital outputs. Communication is CAN-based — no onboard Industrial Ethernet port (0 hardware interfaces for Ethernet). If your plant runs PROFINET or EtherNet/IP, you will need an optional fieldbus adapter module. The I/O count is generous for a drive this size; you can handle most feedback and control signals without an external I/O block.","metaTitle":"ABB 3AXD50000145829 ACS880-17 Drive, 710 kW, 1010 A","metaDescription":"ABB ACS880-17 regenerative drive, 710 kW normal use (1010 A), 500 kW heavy duty. Active production. SCIP 944D8A5E. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Inverter / VFD"],"specifications":{"SCIP":"944D8A5E-036D-404E-9036-0D3C1EA703AD Finland","Altitude":"1000 m","Includes":"Control unit","Frame Size":"2xR8i+2xR8i","Power Factor":"1","Sound dB (A)":"77 dB(A)","Analog Inputs":"4","Frequency (f)":"48 ... 63 Hz","WEEE Category":"4. Large Equipment (Any External Dimension More Than 50 cm)","Analog Outputs":"4","lifecycle_stage":"current","Number of Phases":"3-phase","Temperature Rating":"Maximum 40 °C","Ecodesign Exemption":"Energy efficiency data is not provided for the drive. The regenerative drives are exempt from the EU ecodesign requirements (Regulation EU/2019/1781, §2.3.c).","Enclosure Type NEMA":"Type1","Input Voltage (Uin)":"380 ... 500 V","Degree of Protection":"IP22","Apparent Power Output":"875 kV·A","Communication Protocol":"CAN","Operating Humidity (RHamβ)":"5 ... 95","Multiple Battery Information":"Lithium Coin, BR2032, 2pcs, 3V, 200mAh, 3g","Number of Digital In/Outputs":"14 / 10","Number of Hardware Interfaces":"Industrial Ethernet 0","Output Power, Normal Use (Pn)":"710 kW","Output Current, Normal Use (In)":"1010 A","Output Power, Heavy-Duty Use (PhD)":"500 kW","Output Current, Heavy-Duty Use (IhD)":"755 A","Output Power, Light-Overload Use (PlD)":"630 kW","Output Current, Light-Overload Use (IlD)":"970 A","Technical UL/Output Power, Normal Use (UL)":"900 Hp","Technical UL/Output Current, Normal Use (UL)":"1010 A","Technical UL/Output Power, Heavy-Duty Use (UL)":"600 Hp","Technical UL/Output Current, Heavy-Duty Use (UL)":"755 A","Technical UL/Output Power, Light-Overload Use (UL)":"800 Hp","Technical UL/Output Current, Light-Overload Use (UL)":"970 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50000145829","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50000145829/alternatives.json"},"ai":{"faq":[{"question":"What is the SCIP number for this drive?","answer":"SCIP: 944D8A5E-036D-404E-9036-0D3C1EA703AD, registered in Finland."},{"question":"What compliance documentation does ABB provide for this drive?","answer":"SCIP number is listed; the drive is exempt from EU ecodesign energy-efficiency requirements (Regulation 2019/1781 §2.3.c) as a regenerative type. WEEE category 4 applies. No RoHS/REACH/UL certificate numbers are in this record, but ABB typically provides them on request."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50000145829","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50000145829 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}