{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50000145850","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50000145850","canonicalUrl":"https://aoctrl.com/abb/3AXD50000145850","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50000145850","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACS880-17 regenerative drive, 3AXD50000145850, 380-500 V 3-phase, 1400 kW / 1980 A normal use, IP22, Type 1, active.","salesMarkdown":"The 3AXD50000145850: Normal-use output is 1400 kW at 1980 A; heavy-duty use is 1000 kW at 1481 A; light-overload use is 1300 kW at 1901 A. The UL equivalent ratings track the same current figures at 1750 Hp, 1250 Hp, and 1500 Hp respectively. For a procurement decision, the heavy-duty figure governs continuous motor load applications where the drive must hold torque through a stalled or high-inertia start — if the motor nameplate exceeds 1481 A at the rated voltage, this frame is undersized for that duty class. ## Environmental and installation limits Maximum ambient temperature is 40 °C, operating humidity 5–95 % RH, altitude 1000 m without derating. Enclosure is IP22 with NEMA Type 1 — suitable for indoor, non-condensing environments but not for washdown or dust-heavy areas. Sound pressure level is 78 dB(A); plan for panel attenuation if the drive is near operator stations. Four analog inputs, four analog outputs, 14 digital inputs, 10 digital outputs. Communication is CAN; no onboard Industrial Ethernet. The control unit is included in the frame. Two lithium coin cells (BR2032, 3 V, 200 mAh) back up real-time clock and parameter storage — verify replacement interval per site maintenance schedule. ## Regulatory and compliance notes SCIP number 944D8A5E-036D-404E-9036-0D3C1EA703AD Finland. WEEE category 4 (Large Equipment, any external dimension >50 cm). This regenerative drive is exempt from EU ecodesign energy-efficiency requirements under Regulation EU/2019/1781 §2.3.c.","metaTitle":"ABB 3AXD50000145850 ACS880-17 Drive, 1400 kW, 1980 A","metaDescription":"ABB ACS880-17-1980A-5 regenerative drive, 1400 kW normal use, 1980 A output. Active production. IP22, Type 1. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Inverter / VFD"],"specifications":{"SCIP":"944D8A5E-036D-404E-9036-0D3C1EA703AD Finland","Altitude":"1000 m","Includes":"Control unit","Frame Size":"3xR8i+3xR8i","Power Factor":"1","Sound dB (A)":"78 dB(A)","Analog Inputs":"4","Frequency (f)":"48 ... 63 Hz","WEEE Category":"4. Large Equipment (Any External Dimension More Than 50 cm)","Analog Outputs":"4","lifecycle_stage":"current","Number of Phases":"3-phase","Temperature Rating":"Maximum 40 °C","Ecodesign Exemption":"Energy efficiency data is not provided for the drive. The regenerative drives are exempt from the EU ecodesign requirements (Regulation EU/2019/1781, §2.3.c).","Enclosure Type NEMA":"Type1","Input Voltage (Uin)":"380 ... 500 V","Degree of Protection":"IP22","Apparent Power Output":"1715 kV·A","Communication Protocol":"CAN","Operating Humidity (RHamβ)":"5 ... 95","Multiple Battery Information":"Lithium Coin, BR2032, 2pcs, 3V, 200mAh, 3g","Number of Digital In/Outputs":"14 / 10","Number of Hardware Interfaces":"Industrial Ethernet 0","Output Power, Normal Use (Pn)":"1400 kW","Output Current, Normal Use (In)":"1980 A","Output Power, Heavy-Duty Use (PhD)":"1000 kW","Output Current, Heavy-Duty Use (IhD)":"1481 A","Output Power, Light-Overload Use (PlD)":"1300 kW","Output Current, Light-Overload Use (IlD)":"1901 A","Technical UL/Output Power, Normal Use (UL)":"1750 Hp","Technical UL/Output Current, Normal Use (UL)":"1980 A","Technical UL/Output Power, Heavy-Duty Use (UL)":"1250 Hp","Technical UL/Output Current, Heavy-Duty Use (UL)":"1481 A","Technical UL/Output Power, Light-Overload Use (UL)":"1500 Hp","Technical UL/Output Current, Light-Overload Use (UL)":"1901 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50000145850","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50000145850/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings of the 3AXD50000145850?","answer":"Normal-use output is 1400 kW at 1980 A; heavy-duty is 1000 kW at 1481 A; light-overload is 1300 kW at 1901 A. Input is 380–500 V three-phase, 48–63 Hz."},{"question":"What is the SCIP number for this drive?","answer":"SCIP: 944D8A5E-036D-404E-9036-0D3C1EA703AD Finland."},{"question":"What is the maximum operating altitude?","answer":"1000 m without derating."},{"question":"What enclosure and protection rating does it have?","answer":"NEMA Type 1, IP22."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50000145850","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50000145850 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}