{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50000145867","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50000145867","canonicalUrl":"https://aoctrl.com/abb/3AXD50000145867","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50000145867","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACS880-17 series, regenerative drive, order code 3AXD50000145867, 1600 kW normal use, 2270 A output, 380-500 V 3-phase.","salesMarkdown":"The ABB 3AXD50000145867 is a regenerative drive rated for 1600 kW normal-use output at 2270 A, fed from a 380-500 V 3-phase supply. It is built in a 3xR8i+3xR8i frame with NEMA 1 enclosure and IP22 protection. The drive carries three distinct duty ratings: 1600 kW / 2270 A for normal use, 1500 kW / 2179 A for light-overload, and 1200 kW / 1698 A for heavy-duty. The heavy-duty figure governs continuous motor torque at high starting loads or demanding cycles; the light-overload rating covers applications with occasional peak demand above the normal curve. ## Duty ratings and real-world fit The light-overload figure (1500 kW) sits between them and matches applications like pumps or fans where occasional peak demand is the exception, not the rule. ## Environmental limits and installation constraints Rated for a maximum ambient of 40 °C, altitude up to 1000 m without derating, and operating humidity of 5-95% non-condensing. The 78 dB(A) sound level at full load means hearing protection is advisable in the drive room. The regenerative design is exempt from EU ecodesign efficiency reporting (Regulation EU/2019/1781, §2.3.c) — no energy-efficiency class to declare. ## I/O and communication summary The drive includes 14 digital I/O (10 outputs), 4 analog inputs, and 4 analog outputs. Communication is via CAN bus; no onboard Industrial Ethernet. The control unit is included. Two lithium coin cells (BR2032, 3 V, 200 mAh each) back up the real-time clock and parameter storage.","metaTitle":"ABB 3AXD50000145867 ACS880-17 Drive, 1600 kW, 2270 A","metaDescription":"ABB ACS880-17-2270A-5 regenerative drive, 1600 kW normal use, 2270 A output, 380-500 V 3-phase. Active production, NEMA 1, IP22. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Inverter / VFD"],"specifications":{"SCIP":"944D8A5E-036D-404E-9036-0D3C1EA703AD Finland","Altitude":"1000 m","Includes":"Control unit","Frame Size":"3xR8i+3xR8i","Power Factor":"1","Sound dB (A)":"78 dB(A)","Analog Inputs":"4","Frequency (f)":"48 ... 63 Hz","WEEE Category":"4. Large Equipment (Any External Dimension More Than 50 cm)","Analog Outputs":"4","lifecycle_stage":"current","Number of Phases":"3-phase","Temperature Rating":"Maximum 40 °C","Ecodesign Exemption":"Energy efficiency data is not provided for the drive. The regenerative drives are exempt from the EU ecodesign requirements (Regulation EU/2019/1781, §2.3.c).","Enclosure Type NEMA":"Type1","Input Voltage (Uin)":"380 ... 500 V","Degree of Protection":"IP22","Apparent Power Output":"1966 kV·A","Communication Protocol":"CAN","Operating Humidity (RHamβ)":"5 ... 95","Multiple Battery Information":"Lithium Coin, BR2032, 2pcs, 3V, 200mAh, 3g","Number of Digital In/Outputs":"14 / 10","Number of Hardware Interfaces":"Industrial Ethernet 0","Output Power, Normal Use (Pn)":"1600 kW","Output Current, Normal Use (In)":"2270 A","Output Power, Heavy-Duty Use (PhD)":"1200 kW","Output Current, Heavy-Duty Use (IhD)":"1698 A","Output Power, Light-Overload Use (PlD)":"1500 kW","Output Current, Light-Overload Use (IlD)":"2179 A","Technical UL/Output Power, Normal Use (UL)":"2000 Hp","Technical UL/Output Current, Normal Use (UL)":"2270 A","Technical UL/Output Power, Heavy-Duty Use (UL)":"1500 Hp","Technical UL/Output Current, Heavy-Duty Use (UL)":"1698 A","Technical UL/Output Power, Light-Overload Use (UL)":"1900 Hp","Technical UL/Output Current, Light-Overload Use (UL)":"2179 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50000145867","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50000145867/alternatives.json"},"ai":{"faq":[{"question":"What are the key electrical ratings?","answer":"Normal-use output is 1600 kW at 2270 A; heavy-duty is 1200 kW at 1698 A; light-overload is 1500 kW at 2179 A. Input is 380-500 V 3-phase, 48-63 Hz."},{"question":"What enclosure and protection rating does it have?","answer":"NEMA Type 1 enclosure with IP22 degree of protection — indoor use, no washdown capability."},{"question":"What is the SCIP number for this drive?","answer":"SCIP: 944D8A5E-036D-404E-9036-0D3C1EA703AD, registered in Finland."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50000145867","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50000145867 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}