{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50000145973","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50000145973","canonicalUrl":"https://aoctrl.com/abb/3AXD50000145973","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50000145973","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACS880-17 regenerative drive, 3AXD50000145973, 2200 kW / 2230 A normal use, 525-690 V 3-phase input, IP22, Type 1.","salesMarkdown":"The ABB 3AXD50000145973 is rated for 2200 kW normal-use output power and 2230 A normal-use output current on a 525 to 690 V three-phase supply. It is a frame 4xR8i+4xR8i unit with the control module included, built for applications that need to feed regenerated energy back into the line rather than dump it across a brake resistor. Normal-use output current is 2230 A, with a corresponding heavy-duty rating of 1668 A and a light-overload rating of 2141 A. The heavy-duty figure governs continuous motor load in a constant-torque application; the light-overload figure covers variable-torque loads like pumps and fans where occasional overload is expected. Apparent power output sits at 2665 kV·A, which gives you the transformer or generator sizing number for the line side. Input voltage range is 525 to 690 V AC, three-phase, 48 to 63 Hz. Maximum ambient temperature is 40 °C, altitude 1000 m without derating. The drive carries 4 analog inputs and 4 analog outputs, plus 14 digital I/O and 10 digital outputs. The battery pack is two BR2032 lithium coins, 3 V each, 200 mAh — keep spares on the shelf for the control board memory backup. ## Regulatory notes The SCIP number is 944D8A5E-036D-404E-9036-0D3C1EA703AD Finland, which is the EU waste framework declaration for the article. WEEE category is 4 (Large Equipment). The regenerative design is exempt from EU ecodesign efficiency requirements under Regulation EU/2019/1781 §2.3.c, so no energy-efficiency class is published for this drive.","metaTitle":"ABB 3AXD50000145973 ACS880-17 Drive, 2200 kW, 2230 A","metaDescription":"ABB ACS880-17-2230A-7 regenerative drive, 2200 kW normal use, 2230 A output, 525-690 V input. Active production. Sourced to order. RFQ for lead time.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 600V"],"specifications":{"SCIP":"944D8A5E-036D-404E-9036-0D3C1EA703AD Finland","Altitude":"1000 m","Includes":"Control unit","Frame Size":"4xR8i+4xR8i","Power Factor":"1","Sound dB (A)":"79 dB(A)","Analog Inputs":"4","Frequency (f)":"48 ... 63 Hz","WEEE Category":"4. Large Equipment (Any External Dimension More Than 50 cm)","Analog Outputs":"4","lifecycle_stage":"current","Number of Phases":"3-phase","Temperature Rating":"Maximum 40 °C","Ecodesign Exemption":"Energy efficiency data is not provided for the drive. The regenerative drives are exempt from the EU ecodesign requirements (Regulation EU/2019/1781, §2.3.c).","Enclosure Type NEMA":"Type1","Input Voltage (Uin)":"525 ... 690 V","Degree of Protection":"IP22","Apparent Power Output":"2665 kV·A","Communication Protocol":"CAN","Operating Humidity (RHamβ)":"5 ... 95","Multiple Battery Information":"Lithium Coin, BR2032, 2pcs, 3V, 200mAh, 3g","Number of Digital In/Outputs":"14 / 10","Number of Hardware Interfaces":"Industrial Ethernet 0","Output Power, Normal Use (Pn)":"2200 kW","Output Current, Normal Use (In)":"2230 A","Output Power, Heavy-Duty Use (PhD)":"1600 kW","Output Current, Heavy-Duty Use (IhD)":"1668 A","Output Power, Light-Overload Use (PlD)":"2000 kW","Output Current, Light-Overload Use (IlD)":"2141 A","Technical UL/Output Power, Normal Use (UL)":"2500 Hp","Technical UL/Output Current, Normal Use (UL)":"2230 A","Technical UL/Output Power, Heavy-Duty Use (UL)":"1750 Hp","Technical UL/Output Current, Heavy-Duty Use (UL)":"1668 A","Technical UL/Output Power, Light-Overload Use (UL)":"2250 Hp","Technical UL/Output Current, Light-Overload Use (UL)":"2141 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50000145973","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50000145973/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings of this drive?","answer":"Normal-use output is 2200 kW and 2230 A. Heavy-duty output is 1600 kW and 1668 A. Light-overload output is 2000 kW and 2141 A. Input is 525-690 V three-phase, 48-63 Hz."},{"question":"What enclosure and protection rating does this drive have?","answer":"IP22 with a NEMA Type 1 enclosure. Indoor installation only, maximum ambient 40 °C, altitude 1000 m without derating."},{"question":"What communication protocols does this drive support?","answer":"CAN communication is built in. There are no Industrial Ethernet interfaces on this variant; optional fieldbus adapters are required for PROFINET, EtherNet/IP, or similar protocols."},{"question":"What is the SCIP number for this drive?","answer":"SCIP: 944D8A5E-036D-404E-9036-0D3C1EA703AD Finland. WEEE category is 4 (Large Equipment)."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50000145973","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50000145973 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}