{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50000146123","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50000146123","canonicalUrl":"https://aoctrl.com/abb/3AXD50000146123","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50000146123","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACS880-37 low-harmonic drive, 3AXD50000146123, 355 kW / 503 A normal use, 380-500 VAC 3-phase, Frame R11, IP22, CAN.","salesMarkdown":"## Load Ratings and Duty Selection The 3AXD50000146123: Three duty ratings are specified: normal-use (Pn 355 kW, In 503 A), heavy-duty (PhD 315 kW, IhD 460 A), and light-overload (PlD 355 kW, IlD 492 A). The heavy-duty figure governs continuous motor load for applications like conveyors or pumps where overload margin is needed; the normal-use rating suits variable-torque loads such as fans and centrifugal pumps. UL heavy-duty ratings are 400 Hp and 483 A. ## Enclosure, Environment, and Compliance The drive is housed in Frame R11 with an IP22 degree of protection and NEMA Type 1 enclosure, suitable for indoor installation in clean, dry environments. Maximum ambient temperature is 40 °C, altitude 1000 m, and operating humidity 5-95% non-condensing. Sound level is 77 dB(A). The low-harmonic design is exempt from EU ecodesign requirements (Regulation EU/2019/1781, §2.3.d). SCIP number is 9ECED1FE-316A-4BF4-991E-2606BB5FE13A Finland. Built-in I/O includes 2 analog inputs, 2 analog outputs, 7 digital inputs, and 5 digital outputs. Communication is via CAN protocol; no onboard Industrial Ethernet port. A lithium coin cell (CR2032, 2 pcs) backs the real-time clock. The control unit is included in the delivery.","metaTitle":"ABB 3AXD50000146123 ACS880-37 Drive, 355 kW, 503 A","metaDescription":"ABB ACS880-37 low-harmonic drive, 355 kW normal use, 503 A output current. Active production. Frame R11, IP22, CAN protocol. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Inverter / VFD"],"specifications":{"SCIP":"9ECED1FE-316A-4BF4-991E-2606BB5FE13A Finland","Altitude":"1000 m","Includes":"Control unit","Frame Size":"R11","Power Factor":"1","Sound dB (A)":"77 dB(A)","Analog Inputs":"2","Frequency (f)":"48 ... 63 Hz","WEEE Category":"4. Large Equipment (Any External Dimension More Than 50 cm)","Analog Outputs":"2","lifecycle_stage":"current","Number of Phases":"3-phase","Temperature Rating":"Maximum 40 °C","Ecodesign Exemption":"Energy efficiency data is not provided for the drive. The low-harmonic drives are exempt from the EU ecodesign requirements (Regulation EU/2019/1781, §2.3.d).","Enclosure Type NEMA":"Type1","Input Voltage (Uin)":"380 ... 500 V","Degree of Protection":"IP22","Apparent Power Output":"436 kV·A","Communication Protocol":"CAN","Operating Humidity (RHamβ)":"5 ... 95","Multiple Battery Information":"Lithium Coin, CR2032, 2pcs, 3V, 220mAh, 6g","Number of Digital In/Outputs":"7 / 5","Number of Hardware Interfaces":"Industrial Ethernet 0","Output Power, Normal Use (Pn)":"355 kW","Output Current, Normal Use (In)":"503 A","Output Power, Heavy-Duty Use (PhD)":"315 kW","Output Current, Heavy-Duty Use (IhD)":"460 A","Output Power, Light-Overload Use (PlD)":"355 kW","Output Current, Light-Overload Use (IlD)":"492 A","Technical UL/Output Power, Normal Use (UL)":"- Hp","Technical UL/Output Current, Normal Use (UL)":"- A","Technical UL/Output Power, Heavy-Duty Use (UL)":"400 Hp","Technical UL/Output Current, Heavy-Duty Use (UL)":"483 A","Technical UL/Output Power, Light-Overload Use (UL)":"400 Hp","Technical UL/Output Current, Light-Overload Use (UL)":"483 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50000146123","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50000146123/alternatives.json"},"ai":{"faq":[{"question":"What are the key power and current ratings?","answer":"Normal-use output is 355 kW and 503 A; heavy-duty is 315 kW and 460 A; light-overload is 355 kW and 492 A. UL heavy-duty rating is 400 Hp and 483 A."},{"question":"What is the input voltage and frequency range?","answer":"Input voltage is 380-500 VAC three-phase, 48-63 Hz."},{"question":"What enclosure and protection rating does it have?","answer":"Frame R11 with IP22 protection and NEMA Type 1 enclosure."},{"question":"What communication protocols are supported?","answer":"CAN protocol is standard; no onboard Industrial Ethernet."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50000146123","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50000146123 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}