{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50000146192","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50000146192","canonicalUrl":"https://aoctrl.com/abb/3AXD50000146192","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50000146192","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACS880-37 series, 3AXD50000146192, 400 kW / 430 A normal-use drive, 525-690 V input, frame size R11, IP22.","salesMarkdown":"The 3AXD50000146192: The 430 A normal-use current (In) and 400 kW output power (Pn) define the continuous duty envelope for a standard motor load. Light-overload use sits at 420 A and 400 kW, splitting the difference. The UL listing confirms 370 A heavy-duty (350 Hp) and 420 A light-overload (450 Hp), so the drive carries the same ratings under UL evaluation. Input voltage spans 525 to 690 V at 48 to 63 Hz, three-phase. The apparent power output is 514 kV·A, which gives a headroom check for transformer or generator sizing. Enclosure is IP22 with NEMA Type 1 — drip-proof, indoor, no washdown. Ambient limit is 40 °C maximum; altitude ceiling is 1000 m without derating. ## I/O and interfaces The drive includes the control unit. It carries 2 analog inputs, 2 analog outputs, 7 digital inputs, and 5 digital outputs. Communication is CAN-based; there is no onboard Industrial Ethernet interface. Two CR2032 lithium coin cells back up the real-time clock and parameter storage. SCIP number is 9ECED1FE-316A-4BF4-991E-2606BB5FE13A (Finland). The drive is exempt from EU ecodesign energy-efficiency requirements under Regulation EU/2019/1781 §2.3.d because it is a low-harmonic type. WEEE category 4 (large equipment). Sound level is 77 dB(A).","metaTitle":"3AXD50000146192 ABB ACS880-37-0430A-7 Drive, 400 kW, 430 A,","metaDescription":"Active ABB ACS880-37-0430A-7 drive, 400 kW normal use, 430 A output, 525-690 V input, frame size R11. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 600V"],"specifications":{"SCIP":"9ECED1FE-316A-4BF4-991E-2606BB5FE13A Finland","Altitude":"1000 m","Includes":"Control unit","Frame Size":"R11","Power Factor":"1","Sound dB (A)":"77 dB(A)","Analog Inputs":"2","Frequency (f)":"48 ... 63 Hz","WEEE Category":"4. Large Equipment (Any External Dimension More Than 50 cm)","Analog Outputs":"2","lifecycle_stage":"current","Number of Phases":"3-phase","Temperature Rating":"Maximum 40 °C","Ecodesign Exemption":"Energy efficiency data is not provided for the drive. The low-harmonic drives are exempt from the EU ecodesign requirements (Regulation EU/2019/1781, §2.3.d).","Enclosure Type NEMA":"Type1","Input Voltage (Uin)":"525 ... 690 V","Degree of Protection":"IP22","Apparent Power Output":"514 kV·A","Communication Protocol":"CAN","Operating Humidity (RHamβ)":"5 ... 95","Multiple Battery Information":"Lithium Coin, CR2032, 2pcs, 3V, 220mAh, 6g","Number of Digital In/Outputs":"7 / 5","Number of Hardware Interfaces":"Industrial Ethernet 0","Output Power, Normal Use (Pn)":"400 kW","Output Current, Normal Use (In)":"430 A","Output Power, Heavy-Duty Use (PhD)":"355 kW","Output Current, Heavy-Duty Use (IhD)":"370 A","Output Power, Light-Overload Use (PlD)":"400 kW","Output Current, Light-Overload Use (IlD)":"420 A","Technical UL/Output Power, Normal Use (UL)":"- Hp","Technical UL/Output Current, Normal Use (UL)":"- A","Technical UL/Output Power, Heavy-Duty Use (UL)":"350 Hp","Technical UL/Output Current, Heavy-Duty Use (UL)":"370 A","Technical UL/Output Power, Light-Overload Use (UL)":"450 Hp","Technical UL/Output Current, Light-Overload Use (UL)":"420 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50000146192","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50000146192/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings for this drive?","answer":"Normal-use output is 400 kW at 430 A; heavy-duty is 355 kW at 370 A. Input voltage is 525 to 690 V three-phase. Frame size is R11."},{"question":"What is the SCIP number for this drive?","answer":"The SCIP number is 9ECED1FE-316A-4BF4-991E-2606BB5FE13A, registered in Finland."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50000146192","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50000146192 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}