{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50000157983","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50000157983","canonicalUrl":"https://aoctrl.com/abb/3AXD50000157983","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50000157983","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACS880-17-0145A-3 regenerative drive, 75 kW / 145 A normal use, 380-415 VAC, 3-phase, Frame R8, IP22, NEMA 1.","salesMarkdown":"## Drive identity and key ratings The ABB ACS880-17-0145A-3 (3AXD50000157983) is a regenerative drive delivering 75 kW normal-use output at 145 A, with heavy-duty capability of 55 kW at 105 A. It runs on a 380 to 415 VAC, 3-phase supply and is housed in a Frame R8 enclosure rated IP22 and NEMA Type 1. The 75 kW normal-use (Pn) rating matches a standard 100 hp induction motor on a pump or fan. The 145 A normal-use current (In) and 105 A heavy-duty current (IhD) are the numbers to check against your motor nameplate full-load amps. Ambient temperature is limited to 40 °C maximum; above that, derate per the drive's thermal curve. Altitude rating of 1000 m means no derating needed at most sites, but above that you'll need to reduce current per IEC guidelines. ## Integration and I/O The drive includes 2 analog inputs and 2 analog outputs for speed reference or process feedback, plus 7 digital inputs and 5 digital outputs for start/stop, fault reset, and status indication. Communication is via CAN; no onboard Ethernet, so if you need fieldbus, plan for an optional adapter module. The control unit is included. Two lithium coin cells (CR2032) back the real-time clock and parameter storage — expect to replace them every few years during maintenance. The regenerative design is exempt from EU ecodesign requirements (Regulation EU/2019/1781, §2.3.c), so no energy-efficiency class is declared. The SCIP substance declaration (82D82DAE-9725-4373-865D-AA949B97DE50 Finland) is on file for REACH compliance.","metaTitle":"3AXD50000157983 ABB ACS880-17-0145A-3 Drive, 75 kW, 145 A, F","metaDescription":"ABB ACS880-17-0145A-3 regenerative drive, 75 kW normal-use output, 145 A, 380-415 VAC, 3-phase, IP22, NEMA 1, Frame R8. Active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"SCIP":"82D82DAE-9725-4373-865D-AA949B97DE50 Finland","Altitude":"1000 m","Includes":"Control unit","Frame Size":"R8","Power Factor":"1","Sound dB (A)":"70 dB(A)","Analog Inputs":"2","Frequency (f)":"48 ... 63 Hz","WEEE Category":"4. Large Equipment (Any External Dimension More Than 50 cm)","Analog Outputs":"2","lifecycle_stage":"current","Number of Phases":"3-phase","Temperature Rating":"Maximum 40 °C","Ecodesign Exemption":"Energy efficiency data is not provided for the drive. The regenerative drives are exempt from the EU ecodesign requirements (Regulation EU/2019/1781, §2.3.c).","Enclosure Type NEMA":"Type1","Input Voltage (Uin)":"380 ... 415 V","Degree of Protection":"IP22","Apparent Power Output":"100 kV·A","Communication Protocol":"CAN","Operating Humidity (RHamβ)":"5 ... 95","Multiple Battery Information":"Lithium Coin, CR2032, 2pcs, 3V, 220mAh, 6g","Number of Digital In/Outputs":"7 / 5","Number of Hardware Interfaces":"Industrial Ethernet 0","Output Power, Normal Use (Pn)":"75 kW","Output Current, Normal Use (In)":"145 A","Output Power, Heavy-Duty Use (PhD)":"55 kW","Output Current, Heavy-Duty Use (IhD)":"105 A","Output Power, Light-Overload Use (PlD)":"75 kW","Output Current, Light-Overload Use (IlD)":"138 A","Technical UL/Output Power, Normal Use (UL)":"- Hp","Technical UL/Output Current, Normal Use (UL)":"- A","Technical UL/Output Power, Heavy-Duty Use (UL)":"- Hp","Technical UL/Output Current, Heavy-Duty Use (UL)":"- A","Technical UL/Output Power, Light-Overload Use (UL)":"- Hp","Technical UL/Output Current, Light-Overload Use (UL)":"- A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50000157983","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50000157983/alternatives.json"},"ai":{"faq":[{"question":"What are the key power ratings of this drive?","answer":"Normal-use output is 75 kW at 145 A; heavy-duty output is 55 kW at 105 A; light-overload output is 75 kW at 138 A."},{"question":"What input voltage and phases does it require?","answer":"It requires 380 to 415 VAC, 3-phase, 48 to 63 Hz."},{"question":"What is the enclosure protection rating?","answer":"IP22 with NEMA Type 1 enclosure, suitable for indoor installation where no water spray is present."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50000157983","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50000157983 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}