{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50000158027","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50000158027","canonicalUrl":"https://aoctrl.com/abb/3AXD50000158027","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50000158027","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACS880-17 regenerative drive, 3AXD50000158027, 75 kW / 124 A normal-use, 55 kW / 96 A heavy-duty, 380–500 V, IP22, frame R8.","salesMarkdown":"ABB 3AXD50000158027 is a regenerative drive rated 75 kW normal-use output (124 A) on a 380–500 V three-phase supply. Heavy-duty use drops to 55 kW (96 A); light-overload use holds at 75 kW (118 A). ## Load-duty fit and derating Three duty ratings let you match the drive to the load profile. Normal-use (Pn 75 kW, In 124 A) covers constant-torque applications like conveyors. Heavy-duty (PhD 55 kW, IhD 96 A) handles variable-torque loads such as pumps and fans with occasional overloads. Light-overload (PlD 75 kW, IlD 118 A) suits applications with infrequent peak demands. The regenerative design recovers braking energy back to the line, which matters for overhauling loads or frequent deceleration cycles. ## Input and environmental limits Runs on 380–500 VAC, 48–63 Hz. Ambient temperature max 40 °C; altitude rated to 1000 m without derating. Humidity range 5–95% non-condensing. Sound level 70 dB(A). The drive is exempt from EU ecodesign requirements (Regulation EU/2019/1781, §2.3.c) because regenerative units fall outside the scope. Built-in I/O: 7 digital inputs, 5 digital outputs, 2 analog inputs, 2 analog outputs. Communication via CAN. No onboard Industrial Ethernet; add an optional fieldbus adapter if PROFINET or EtherNet/IP is needed.","metaTitle":"ABB 3AXD50000158027 ACS880-17 Drive, 75 kW, 124 A","metaDescription":"Active ABB ACS880-17 regenerative drive, 75 kW normal-use (124 A), 55 kW heavy-duty (96 A). 380-500 V, IP22, Type 1, frame R8. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Inverter / VFD"],"specifications":{"SCIP":"82D82DAE-9725-4373-865D-AA949B97DE50 Finland","Altitude":"1000 m","Includes":"Control unit","Frame Size":"R8","Power Factor":"1","Sound dB (A)":"70 dB(A)","Analog Inputs":"2","Frequency (f)":"48 ... 63 Hz","WEEE Category":"4. Large Equipment (Any External Dimension More Than 50 cm)","Analog Outputs":"2","lifecycle_stage":"current","Number of Phases":"3-phase","Temperature Rating":"Maximum 40 °C","Ecodesign Exemption":"Energy efficiency data is not provided for the drive. The regenerative drives are exempt from the EU ecodesign requirements (Regulation EU/2019/1781, §2.3.c).","Enclosure Type NEMA":"Type1","Input Voltage (Uin)":"380 ... 500 V","Degree of Protection":"IP22","Apparent Power Output":"107 kV·A","Communication Protocol":"CAN","Operating Humidity (RHamβ)":"5 ... 95","Multiple Battery Information":"Lithium Coin, CR2032, 2pcs, 3V, 220mAh, 6g","Number of Digital In/Outputs":"7 / 5","Number of Hardware Interfaces":"Industrial Ethernet 0","Output Power, Normal Use (Pn)":"75 kW","Output Current, Normal Use (In)":"124 A","Output Power, Heavy-Duty Use (PhD)":"55 kW","Output Current, Heavy-Duty Use (IhD)":"96 A","Output Power, Light-Overload Use (PlD)":"75 kW","Output Current, Light-Overload Use (IlD)":"118 A","Technical UL/Output Power, Normal Use (UL)":"- Hp","Technical UL/Output Current, Normal Use (UL)":"- A","Technical UL/Output Power, Heavy-Duty Use (UL)":"75 Hp","Technical UL/Output Current, Heavy-Duty Use (UL)":"96 A","Technical UL/Output Power, Light-Overload Use (UL)":"100 Hp","Technical UL/Output Current, Light-Overload Use (UL)":"124 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50000158027","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50000158027/alternatives.json"},"ai":{"faq":[{"question":"What are the key power ratings for this drive?","answer":"Normal-use output is 75 kW (124 A), heavy-duty is 55 kW (96 A), and light-overload is 75 kW (118 A)."},{"question":"What is the input voltage and frequency range?","answer":"380–500 V three-phase, 48–63 Hz."},{"question":"What enclosure protection does it have?","answer":"IP22 with NEMA Type 1 enclosure."},{"question":"What communication protocol is supported?","answer":"CAN is built in; no onboard Industrial Ethernet."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50000158027","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50000158027 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}