{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50000158089","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50000158089","canonicalUrl":"https://aoctrl.com/abb/3AXD50000158089","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50000158089","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACS880-37-0206A-3, 3AXD50000158089, 110 kW normal-duty drive, 206 A output, R8 frame, IP22, NEMA 1, CAN.","salesMarkdown":"The ABB ACS880-37-0206A-3 (3AXD50000158089) is an R8-frame low-harmonic drive rated for 110 kW normal use (206 A) on a 380–415 V three-phase supply at 48–63 Hz. Heavy-duty use drops to 90 kW (169 A), and light-overload use holds at 110 kW (196 A). The 143 kV·A apparent power output gives headroom for motor inrush and transient loads. Enclosure is IP22 with NEMA 1, so it handles indoor panel environments with limited dust and dripping water. CAN is the onboard fieldbus; no Industrial Ethernet port is fitted, so plan for a gateway or option module if the line uses PROFINET or EtherNet/IP. The drive includes the control unit — no separate ordering needed for basic operation. Ambient temperature is capped at 40 °C, altitude at 1000 m without derating. Onboard I/O: 2 analog inputs, 2 analog outputs, 7 digital inputs, 5 digital outputs. That covers a basic speed reference, feedback, and a few run/stop commands. For more complex sequences, the CAN bus handles peer-to-peer or controller communication. Sound level is 70 dB(A) — audible in a quiet control room but typical for an R8-frame drive at full load. The lithium coin cells (CR2032, 2 pcs) back up the real-time clock and parameter storage; replace them during scheduled maintenance to avoid losing configuration on power loss. ## Sourcing note Submit an RFQ with the 3AXD50000158089 order code and the required quantity; lead time and pricing are confirmed per request.","metaTitle":"3AXD50000158089 ABB ACS880-37-0206A-3 Drive, 110 kW, 206 A,","metaDescription":"ABB ACS880-37-0206A-3 drive, 110 kW normal use, 206 A output, R8 frame. IP22, NEMA 1, CAN. Active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"SCIP":"9ECED1FE-316A-4BF4-991E-2606BB5FE13A Finland","Altitude":"1000 m","Includes":"Control unit","Frame Size":"R8","Power Factor":"1","Sound dB (A)":"70 dB(A)","Analog Inputs":"2","Frequency (f)":"48 ... 63 Hz","WEEE Category":"4. Large Equipment (Any External Dimension More Than 50 cm)","Analog Outputs":"2","lifecycle_stage":"current","Number of Phases":"3-phase","Temperature Rating":"Maximum 40 °C","Ecodesign Exemption":"Energy efficiency data is not provided for the drive. The low-harmonic drives are exempt from the EU ecodesign requirements (Regulation EU/2019/1781, §2.3.d).","Enclosure Type NEMA":"Type1","Input Voltage (Uin)":"380 ... 415 V","Degree of Protection":"IP22","Apparent Power Output":"143 kV·A","Communication Protocol":"CAN","Operating Humidity (RHamβ)":"5 ... 95","Multiple Battery Information":"Lithium Coin, CR2032, 2pcs, 3V, 220mAh, 6g","Number of Digital In/Outputs":"7 / 5","Number of Hardware Interfaces":"Industrial Ethernet 0","Output Power, Normal Use (Pn)":"110 kW","Output Current, Normal Use (In)":"206 A","Output Power, Heavy-Duty Use (PhD)":"90 kW","Output Current, Heavy-Duty Use (IhD)":"169 A","Output Power, Light-Overload Use (PlD)":"110 kW","Output Current, Light-Overload Use (IlD)":"196 A","Technical UL/Output Power, Normal Use (UL)":"- Hp","Technical UL/Output Current, Normal Use (UL)":"- A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50000158089","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50000158089/alternatives.json"},"ai":{"faq":[{"question":"What is the SCIP number for this drive?","answer":"SCIP number is 9ECED1FE-316A-4BF4-991E-2606BB5FE13A, registered in Finland."},{"question":"What are the key power ratings?","answer":"Normal use: 110 kW, 206 A. Heavy-duty use: 90 kW, 169 A. Light-overload use: 110 kW, 196 A. Apparent power output is 143 kV·A."},{"question":"What enclosure protection does it have?","answer":"IP22 with NEMA 1 rating, suitable for indoor panel installation."},{"question":"What communication protocol is onboard?","answer":"CAN is the standard onboard fieldbus. No Industrial Ethernet port is included."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50000158089","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50000158089 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}