{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50000162093","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50000162093","canonicalUrl":"https://aoctrl.com/abb/3AXD50000162093","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50000162093","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACS580 general-purpose drive, 0.75 kW normal-use output, 4.8 A, 200-240 V 3-phase, R1 frame, IP20, CAN interface, IE2 efficiency.","salesMarkdown":"## Rating breakdown The 3AXD50000162093: Normal-use (Pn) output is 0.75 kW at 4.8 A; light-overload use (PlD) matches that at 4.6 A. Input frequency range is 47.5-63 Hz, so it handles weak-grid or generator supply without derating. Standby loss is 14 W; full-load power consumption is 72 W. Power factor at rated load is 0.98. ## I/O and interfaces Two digital inputs and one digital output — no analog I/O on this variant. CAN is the only hardware interface; no Ethernet port.","metaTitle":"3AXD50000162093 ABB ACS580 drive, 0.75 kW, 4.8 A, R1 frame","metaDescription":"ABB ACS580 general-purpose drive, 3AXD50000162093. 0.75 kW normal-use output at 4.8 A, 200-240 V 3-phase. R1 frame, IP20, CAN, IE2. Active production. Sourced to order. RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 240V"],"specifications":{"SCIP":"483516f7-5042-4d76-a918-d7fab20a54ce Finland","Altitude":"1000 m","Includes":"Control unit","Frame Size":"R1","Power Factor":"0.98","Sound dB (A)":"63.10 dB(A)","Standby Loss":"14 W","Analog Inputs":"0","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Module","WEEE Category":"5. Small Equipment (No External Dimension More Than 50 cm)","Analog Outputs":"0","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Temperature Rating":"Maximum 50 °C","Enclosure Type NEMA":"Open Type","Input Voltage (Uin)":"200 ... 240 V","Degree of Protection":"IP20","Apparent Power Output":"1.9 kV·A","Communication Protocol":"CAN","Power Consumption (@Pcons)":"72 W","Operating Humidity (RHamβ)":"5 ... 95","Multiple Battery Information":"No battery / cell included","Number of Digital In/Outputs":"2 / 1","Number of Hardware Interfaces":"Industrial Ethernet 0","Output Power, Normal Use (Pn)":"0.75 kW","Output Current, Normal Use (In)":"4.8 A","Output Power, Heavy-Duty Use (PhD)":"0.55 kW","Output Current, Heavy-Duty Use (IhD)":"3.7 A","Output Power, Light-Overload Use (PlD)":"0.75 kW","Certificates and Declarations/RoHS Date":"20230303","Certificates and Declarations/REACH Date":"20250905","Output Current, Light-Overload Use (IlD)":"4.6 A","Certificates and Declarations/RoHS Information":"Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019","Technical UL/Output Power, Heavy-Duty Use (UL)":"0.75 Hp","Certificates and Declarations/REACH Information":"True - contains substances > 0.1 mass percentage","Technical UL/Output Current, Heavy-Duty Use (UL)":"3.2 A","Technical UL/Output Power, Light-Overload Use (UL)":"1 Hp","Technical UL/Output Current, Light-Overload Use (UL)":"4.6 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50000162093","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50000162093/alternatives.json"},"ai":{"faq":[{"question":"What are the key output ratings for this drive?","answer":"Normal-use output is 0.75 kW at 4.8 A; heavy-duty use is 0.55 kW at 3.7 A. Input is 200-240 V three-phase, 47.5-63 Hz."},{"question":"What communication protocol does this drive support?","answer":"CAN only — no Ethernet interface on this variant."},{"question":"What compliance documentation is available for this drive?","answer":"RoHS compliant per EU Directive 2011/65/EU and Amendment 2015/863; REACH declaration confirms substances above 0.1% mass percentage. UL listing covers heavy-duty and light-overload ratings. SCIP number is 483516f7-5042-4d76-a918-d7fab20a54ce Finland."},{"question":"What is the frame size and protection rating?","answer":"R1 frame, IP20 open type, module mounting."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50000162093","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50000162093 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}