{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50000162123","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50000162123","canonicalUrl":"https://aoctrl.com/abb/3AXD50000162123","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50000162123","rawCanonicalId":null},"summary":{"shortDescription":"ABB drive module, R1 frame, 3-phase 200…240 V input, 2.2 kW / 9.8 A normal-use output, IP20, CAN interface.","salesMarkdown":"The ABB 3AXD50000162123 is a current-production drive module in the R1 frame size, rated for 3-phase 200…240 V input. Normal-use output is 2.2 kW at 9.8 A; heavy-duty use derates to 1.5 kW at 7.8 A. Light-overload use matches normal-use power at 2.2 kW but draws 9.3 A. The unit includes the control unit, communicates over CAN, and is rated IP20 for panel-mount environments. The normal-use output current of 9.8 A is the figure to size motor protection and cabling for continuous duty. Heavy-duty use at 7.8 A applies for applications requiring higher torque at low speed or frequent starts — the 1.5 kW power limit reflects that thermal headroom. Light-overload use at 9.3 A sits between normal and heavy-duty for intermittent overload profiles. The 0.98 power factor and 140 W power consumption give the panel designer the numbers for upstream transformer and cooling sizing. Standby loss of 15 W matters for systems that idle for long periods — it's the heat the enclosure must shed even when the drive isn't running a load. Current-production part. The R1 frame and CAN interface are stable.","metaTitle":"ABB 3AXD50000162123 Drive Module, R1 Frame, 2.2 kW, 9.8 A","metaDescription":"Current-production ABB drive module 3AXD50000162123, R1 frame, 2.2 kW normal-use output at 9.8 A. SCIP 483516f7-5042-4d76-a918-d7fab20a54ce Finland. RoHS/REACH/UL documentation ava","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 240V"],"specifications":{"SCIP":"483516f7-5042-4d76-a918-d7fab20a54ce Finland","Altitude":"1000 m","Includes":"Control unit","Frame Size":"R1","Power Factor":"0.98","Sound dB (A)":"63.10 dB(A)","Standby Loss":"15 W","Analog Inputs":"0","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Module","WEEE Category":"5. Small Equipment (No External Dimension More Than 50 cm)","Analog Outputs":"0","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Temperature Rating":"Maximum 50 °C","Enclosure Type NEMA":"Open Type","Input Voltage (Uin)":"200 ... 240 V","Degree of Protection":"IP20","Apparent Power Output":"3.9 kV·A","Communication Protocol":"CAN","Power Consumption (@Pcons)":"140 W","Operating Humidity (RHamβ)":"5 ... 95","Multiple Battery Information":"No battery / cell included","Number of Digital In/Outputs":"2 / 1","Number of Hardware Interfaces":"Industrial Ethernet 0","Output Power, Normal Use (Pn)":"2.2 kW","Output Current, Normal Use (In)":"9.8 A","Output Power, Heavy-Duty Use (PhD)":"1.5 kW","Output Current, Heavy-Duty Use (IhD)":"7.8 A","Output Power, Light-Overload Use (PlD)":"2.2 kW","Certificates and Declarations/RoHS Date":"20230303","Certificates and Declarations/REACH Date":"20250905","Output Current, Light-Overload Use (IlD)":"9.3 A","Certificates and Declarations/RoHS Information":"Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019","Technical UL/Output Power, Heavy-Duty Use (UL)":"2 Hp","Certificates and Declarations/REACH Information":"True - contains substances > 0.1 mass percentage","Technical UL/Output Current, Heavy-Duty Use (UL)":"7.5 A","Technical UL/Output Power, Light-Overload Use (UL)":"2 Hp","Technical UL/Output Current, Light-Overload Use (UL)":"9.3 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50000162123","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50000162123/alternatives.json"},"ai":{"faq":[{"question":"What is the SCIP number for this part?","answer":"The SCIP number is 483516f7-5042-4d76-a918-d7fab20a54ce Finland."},{"question":"What compliance documentation is available?","answer":"RoHS compliance follows EU Directive 2011/65/EU and Amendment 2015/863 (dated 20230303). REACH declaration confirms substances above 0.1 mass percentage (dated 20250905). UL technical ratings cover heavy-duty and light-overload use at 2 Hp."},{"question":"What are the key output ratings?","answer":"Normal-use output is 2.2 kW at 9.8 A; heavy-duty use is 1.5 kW at 7.8 A; light-overload use is 2.2 kW at 9.3 A."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50000162123","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50000162123 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}