{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50000211302","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50000211302","canonicalUrl":"https://aoctrl.com/abb/3AXD50000211302","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50000211302","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACS580-01-442A-4, 3AXD50000211302, LV AC general-purpose wall-mounted drive, 250 kW normal-use, 442 A output, 380-480 V 3-phase, Frame R9, IP21, Type 1.","salesMarkdown":"The 3AXD50000211302 is an ABB ACS580-01-442A-4 general-purpose wall-mounted drive rated for 250 kW normal-use output at 442 A, with a 380-480 V 3-phase input and 47-63 Hz line frequency. It's in Frame R9, IP21, NEMA Type 1 enclosure — a current-production unit (lifecycle stage: current). Normal-use (Pn) lands at 250 kW, 442 A — that's the continuous rating for a typical variable-torque load like a pump or fan. Heavy-duty (PhD) drops to 200 kW, 373 A, which is the constant-torque rating you'd size against for a conveyor or extruder. Light-overload (PlD) also shows 200 kW but at 420 A, a slightly higher current for short-duration overloads. Wall-mounted in Frame R9, IP21, NEMA Type 1. That means it's suitable for indoor, dry locations — no washdown, no dust. The Type 1 knockouts simplify conduit entry, but the IP21 rating means you'll want to keep it out of dripping condensate paths. Lithium coin cell (CR2032, 220 mAh) on the control board keeps the real-time clock alive; it's field-replaceable.","metaTitle":"3AXD50000211302 ACS580-01-442A-4 Wall-Mounted Drive, 250 kW","metaDescription":"Active-production ACS580-01 general-purpose drive, 250 kW normal-use, 442 A output, 380-480 V 3-phase input, IP21, Frame R9, wall-mounted. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"Frame Size":"R9","Frequency (f)":"47 ... 63 Hz","Mounting Type":"Wall-mounted","WEEE Category":"4. Large Equipment (Any External Dimension More Than 50 cm)","lifecycle_stage":"current","Number of Phases":"3-phase","Enclosure Type NEMA":"Type1","Input Voltage (Uin)":"380 ... 480 V","Degree of Protection":"IP21","Multiple Battery Information":"Lithium Coin, CR2032, 220 mAh, 3 V, 1 pc, 3 g","Output Power, Normal Use (Pn)":"250 kW","Output Current, Normal Use (In)":"442 A","Output Power, Heavy-Duty Use (PhD)":"200 kW","Output Current, Heavy-Duty Use (IhD)":"373 A","Output Power, Light-Overload Use (PlD)":"200 kW","Output Current, Light-Overload Use (IlD)":"420 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50000211302","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50000211302/alternatives.json"},"ai":{"faq":[{"question":"What is the frame size of 3AXD50000211302?","answer":"Frame R9."},{"question":"What are the input voltage and frequency requirements?","answer":"380-480 V 3-phase, 47-63 Hz."},{"question":"What is the normal-use output power and current?","answer":"250 kW at 442 A."},{"question":"What is the heavy-duty output rating?","answer":"200 kW at 373 A."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50000211302","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50000211302 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}