{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50000268481","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50000268481","canonicalUrl":"https://aoctrl.com/abb/3AXD50000268481","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50000268481","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACQ580-01-114A-2, LV AC wall-mounted drive, 40 Hp light-overload, 114 A, 230 V, Frame R5, IP21, NEMA Type 1.","salesMarkdown":"## Drive selection note for this BOM line The ABB 3AXD50000268481 is an ACQ580-01-114A-2 LV AC wall-mounted drive, sized for water and wastewater applications. It delivers 40 Hp light-overload output (114 A) and 30 Hp heavy-duty (30 A) on a 208–240 V three-phase supply, with an apparent power rating of 45 kV·A. The R5 frame carries an IP21 / NEMA Type 1 enclosure and is rated for a maximum ambient of 40 °C. Standby loss sits at 19 W, and efficiency meets IE2. The light-overload current (114 A) is the figure that governs pump and fan duty — the typical water/wastewater load profile. If your motor is sized for constant-torque or high-starting-torque applications, the heavy-duty rating (30 A) is the binding limit. The 208–240 V input range covers common North American low-voltage three-phase supplies; confirm your line voltage falls within that band. The IP21 enclosure is suitable for indoor, dry panel installations; if the drive is mounted in a washdown area or outdoors, you'll need a higher IP rating.","metaTitle":"ABB 3AXD50000268481 ACQ580-01-114A-2 Drive, 40 Hp, 114 A, 23","metaDescription":"ABB ACQ580-01-114A-2 LV AC wall-mounted drive, 40 Hp light-overload, 114 A output, 230 V input, IP21, active production, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 240V"],"specifications":{"Frame Size":"R5","Standby Loss":"19 W","Frequency (f)":"50/60 Hz","Mounting Type":"Wall-mounting","WEEE Category":"4. Large Equipment (Any External Dimension More Than 50 cm)","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Temperature Rating":"Maximum 40 °C","Enclosure Type NEMA":"Type1","Input Voltage (Uin)":"208 ... 240 V","Degree of Protection":"IP21","Apparent Power Output":"45 kV·A","Technical UL/Output Power, Heavy-Duty Use (UL)":"30 Hp","Technical UL/Output Current, Heavy-Duty Use (UL)":"30 A","Technical UL/Output Power, Light-Overload Use (UL)":"40 Hp","Technical UL/Output Current, Light-Overload Use (UL)":"114 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50000268481","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50000268481/alternatives.json"},"ai":{"faq":[{"question":"What is the frame size of 3AXD50000268481?","answer":"The frame size is R5."},{"question":"What is the standby loss of this drive?","answer":"Standby loss is 19 W."},{"question":"What compliance documentation is available for this drive?","answer":"The drive carries a UL listing (UL output power and current are specified) and is WEEE-category 4 large equipment. RoHS and REACH compliance documentation is typically provided by ABB for the ACQ580 series; confirm with your ABB representative for the specific declaration."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50000268481","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50000268481 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}