{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50000268757","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50000268757","canonicalUrl":"https://aoctrl.com/abb/3AXD50000268757","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50000268757","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACQ580-01 LV AC drive, 3AXD50000268757, 208-240 V 3-phase, 1.5 Hp / 6.6 A light-overload, IP55 Type 12, Frame R1, wall-mount.","salesMarkdown":"The ABB 3AXD50000268757 is a wall-mounted drive built for water and wastewater duty. It runs on 208... 240 V three-phase, delivers 1.5 Hp and 6.6 A under light-overload use, and carries an IP55 Type 12 enclosure. The 6.6 A light-overload figure (PlD) is the continuous rating that governs motor sizing — it's not a peak or surge number. That 1.5 Hp output at 208-240 V matches a standard 1.5 Hp 3-phase motor; if your load profile is heavier or the ambient pushes past 40 °C, you'll need to derate or step up a frame. Standby loss of 13 W is the heat the drive dumps into the panel when it's idling — relevant for enclosure thermal calculations if you're stacking multiple units. IP55 and NEMA Type 12 mean the drive handles direct hose spray and settling dust without an extra enclosure. That's the main reason you'd pick this over a standard IP20 drive in a water/wastewater setting — it saves a cabinet and the associated plumbing for cooling.","metaTitle":"ABB 3AXD50000268757 ACQ580-01 Drive, 1.5 Hp, 6.6 A, IP55","metaDescription":"ABB ACQ580-01 wall-mounted drive for water/wastewater, 208-240 V 3-phase, 1.5 Hp light-overload, IP55 Type 12. Active production, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 240V"],"specifications":{"Frame Size":"R1","Standby Loss":"13 W","Frequency (f)":"50/60 Hz","Mounting Type":"Wall-mounting","WEEE Category":"5. Small Equipment (No External Dimension More Than 50 cm)","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Temperature Rating":"Maximum 40 °C","Enclosure Type NEMA":"Type12","Input Voltage (Uin)":"208 ... 240 V","Degree of Protection":"IP55","Apparent Power Output":"2.6 kV·A","Output Power, Light-Overload Use (PlD)":"1.5 Hp","Output Current, Light-Overload Use (IlD)":"6.6 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50000268757","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50000268757/alternatives.json"},"ai":{"faq":[{"question":"What is the frame size of 3AXD50000268757?","answer":"The drive is Frame Size R1, which is the smallest frame in the ACQ580-01 family, suited for wall-mounting in compact spaces."},{"question":"What is the standby loss of this drive?","answer":"Standby loss is 13 W. This is the power the drive consumes when the motor is not running, relevant for enclosure heat load calculations."},{"question":"What compliance documentation is available for this drive?","answer":"The drive is classified under WEEE Category 5 (Small Equipment). For specific RoHS, REACH, or UL documentation, these are typically provided by ABB upon request through the order channel."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50000268757","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50000268757 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}