{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50000268825","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50000268825","canonicalUrl":"https://aoctrl.com/abb/3AXD50000268825","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50000268825","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACQ580-01 water/wastewater drive, 3AXD50000268825, wall-mount, 208-240 V 3-phase, 40 Hp LO / 30 Hp HD, IP55, NEMA 12, frame R5.","salesMarkdown":"The 3AXD50000268825 is an ABB ACQ580-01 wall-mounted drive sized for 208-240 V three-phase supply, frame R5. It delivers 40 Hp in light-overload duty (114 A continuous) or 30 Hp under heavy-duty use (30 A). The IP55 / NEMA 12 enclosure suits washdown or dusty environments in water and wastewater plants. Heavy-duty current is 30 A, light-overload 114 A — the spread is wide enough that the drive handles a 40 Hp pump at normal load but still delivers 30 Hp continuous in a constant-torque application like a conveyor or mixer. Standby loss of 19 W matters for panel ventilation calculations; that's the heat the drive dissipates when the motor is stopped but the DC bus is live. Input voltage range is 208-240 V three-phase, 50/60 Hz. Ambient maximum is 40 °C — derate above that, as with any IP55 enclosure that relies on convection through the heatsink fins.","metaTitle":"ABB 3AXD50000268825 ACQ580-01-114A-2+B056 VFD, 40 Hp LO, IP5","metaDescription":"ABB ACQ580-01-114A-2+B056 wall-mount VFD, 208-240 V 3-phase, 40 Hp light-overload (114 A), 30 Hp heavy-duty (30 A), IP55, NEMA 12, active production.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 240V"],"specifications":{"Frame Size":"R5","Standby Loss":"19 W","Frequency (f)":"50/60 Hz","Mounting Type":"Wall-mounting","WEEE Category":"4. Large Equipment (Any External Dimension More Than 50 cm)","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Temperature Rating":"Maximum 40 °C","Enclosure Type NEMA":"Type12","Input Voltage (Uin)":"208 ... 240 V","Degree of Protection":"IP55","Apparent Power Output":"45 kV·A","Technical UL/Output Power, Heavy-Duty Use (UL)":"30 Hp","Technical UL/Output Current, Heavy-Duty Use (UL)":"30 A","Technical UL/Output Power, Light-Overload Use (UL)":"40 Hp","Technical UL/Output Current, Light-Overload Use (UL)":"114 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50000268825","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50000268825/alternatives.json"},"ai":{"faq":[{"question":"What is the frame size and mounting?","answer":"Frame R5, wall-mounting. The IP55 / NEMA 12 enclosure is rated for indoor or sheltered outdoor locations."},{"question":"What is the standby loss?","answer":"19 W. This is the power the drive draws with the motor stopped but the DC bus energized — relevant for panel heat load."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50000268825","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50000268825 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}