{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50000268849","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50000268849","canonicalUrl":"https://aoctrl.com/abb/3AXD50000268849","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50000268849","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACQ580-01 wall-mounted drive, frame size R7, 3-phase 208-240 V, 169 A light-overload (60 Hp), IP55, NEMA 12.","salesMarkdown":"The ABB 3AXD50000268849 is an ACQ580-01 wall-mounted drive in frame size R7, built for water and wastewater duty. It runs on 3-phase 208-240 V input at 50/60 Hz and delivers 67 kVA apparent power. The heavy-duty UL rating is 50 A / 50 Hp; light-overload pushes to 169 A / 60 Hp. Enclosure is IP55 / NEMA Type12, so it handles washdown environments without a separate cabinet. Standby loss of 22 W is low enough that ventilation in a small panel isn't a concern, though the drive is wall-mount rated and expects free air around the heatsink. Maximum ambient is 40 °C; if your pump house runs hotter, you'll need to derate or add airflow.","metaTitle":"ABB 3AXD50000268849 ACQ580-01 Drive, R7, 169 A, 60 Hp","metaDescription":"ABB ACQ580-01 wall-mounted drive, frame R7, 3-phase 208-240 V, 169 A light-overload, 60 Hp, IP55, NEMA 12, active production.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 240V"],"specifications":{"Frame Size":"R7","Standby Loss":"22 W","Frequency (f)":"50/60 Hz","Mounting Type":"Wall-mounting","WEEE Category":"4. Large Equipment (Any External Dimension More Than 50 cm)","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Temperature Rating":"Maximum 40 °C","Enclosure Type NEMA":"Type12","Input Voltage (Uin)":"208 ... 240 V","Degree of Protection":"IP55","Apparent Power Output":"67 kV·A","Technical UL/Output Power, Heavy-Duty Use (UL)":"50 Hp","Technical UL/Output Current, Heavy-Duty Use (UL)":"50 A","Technical UL/Output Power, Light-Overload Use (UL)":"60 Hp","Technical UL/Output Current, Light-Overload Use (UL)":"169 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50000268849","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50000268849/alternatives.json"},"ai":{"faq":[{"question":"What enclosure protection does this drive have?","answer":"IP55 and NEMA Type12, suitable for indoor locations with dust, dirt, or hose-down water exposure."},{"question":"What is the standby power loss?","answer":"Standby loss is 22 W, which is low enough for minimal heat contribution in a panel or enclosure."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50000268849","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50000268849 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}