{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50000270958","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50000270958","canonicalUrl":"https://aoctrl.com/abb/3AXD50000270958","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50000270958","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACS580-01-017A-2, frame R1, 5 Hp light-overload, 16.7 A, 208-240 V 3-phase, IP21, NEMA 1, wall-mounting.","salesMarkdown":"The ABB 3AXD50000270958 is an ACS580-01-017A-2 general-purpose wall-mounted drive in frame size R1. It runs on 208-240 V 3-phase at 50/60 Hz and delivers 5 Hp light-overload (16.7 A) or 3 Hp heavy-duty (10.6 A) per UL. The enclosure is IP21 / NEMA Type1, rated for a maximum 40 °C ambient. Standby loss is 13 W, which matters for panel thermal budgeting in a sealed enclosure. Efficiency class IE2 is the baseline for this generation. This part carries an active lifecycle status.","metaTitle":"ABB 3AXD50000270958 ACS580-01-017A-2 Drive, 5 Hp, 16.7 A, 24","metaDescription":"Active ABB ACS580-01 general-purpose drive, frame R1, 5 Hp light-overload, 16.7 A, 208-240 V 3-phase, IP21, NEMA 1. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 240V"],"specifications":{"Frame Size":"R1","Standby Loss":"13 W","Frequency (f)":"50/60 Hz","Mounting Type":"Wall-mounting","WEEE Category":"5. Small Equipment (No External Dimension More Than 50 cm)","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Temperature Rating":"Maximum 40 °C","Enclosure Type NEMA":"Type1","Input Voltage (Uin)":"208 ... 240 V","Degree of Protection":"IP21","Apparent Power Output":"6.7 kV·A","Technical UL/Output Power, Heavy-Duty Use (UL)":"3 Hp","Technical UL/Output Current, Heavy-Duty Use (UL)":"10.6 A","Technical UL/Output Power, Light-Overload Use (UL)":"5 Hp","Technical UL/Output Current, Light-Overload Use (UL)":"16.7 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50000270958","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50000270958/alternatives.json"},"ai":{"faq":[{"question":"What is the standby loss?","answer":"13 W. This is the power dissipated when the drive is energized but not running a motor — relevant for enclosure heat load calculations."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50000270958","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50000270958 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}