{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50000271160","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50000271160","canonicalUrl":"https://aoctrl.com/abb/3AXD50000271160","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50000271160","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACS580-01 series wall-mount general-purpose drive, order code 3AXD50000271160, R5 frame, 3-phase 525...600 V input, UL light-overload 75 Hp / 77 A.","salesMarkdown":"## What lands in the panel The ABB 3AXD50000271160 is the ACS580-01-077A-6 wall-mount general-purpose drive — an R5-frame, 3-phase unit sized for the 525...600 V input class. UL ratings give 75 Hp and 77 A in light-overload use, and 60 Hp with 62 A in heavy-duty use, so the same chassis covers both duty profiles an integrator typically has to plan around. It mounts on the wall in a NEMA Type1 / IP21 enclosure and accepts 50/60 Hz supply on a 525...600 V input, so the panel cutout, cable entry, and branch protection have to be laid out for the 600 V class. ## How the two duty ratings split Heavy-duty use is the conservative number — 60 Hp at 62 A — and that is the figure that should size the branch OCPD and the motor cable when the application is cyclic, high-inertia, or close to the drive's continuous thermal limit. Light-overload use, the UL Pld figure of 75 Hp at 77 A, only applies where the load profile stays inside ABB's light-overload curve. ## Sourcing posture WEEE Category 4 — large equipment with external dimensions over 50 cm — is what governs end-of-life handling on this chassis class, not the operating rating.","metaTitle":"ABB 3AXD50000271160 ACS580-01 Drive, 75 Hp, 600 V","metaDescription":"ABB 3AXD50000271160 — ACS580-01-077A-6 wall-mount drive, UL Pld 75 Hp / 77 A at 525...600 V 3-phase, active production.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Frame Size":"R5","Frequency (f)":"50/60 Hz","Mounting Type":"Wall-mounting","WEEE Category":"4. Large Equipment (Any External Dimension More Than 50 cm)","lifecycle_stage":"current","Number of Phases":"3-phase","Enclosure Type NEMA":"Type1","Input Voltage (Uin)":"525 ... 600 V","Degree of Protection":"IP21","Technical UL/Output Power, Heavy-Duty Use (UL)":"60 Hp","Technical UL/Output Current, Heavy-Duty Use (UL)":"62 A","Technical UL/Output Power, Light-Overload Use (UL)":"75 Hp","Technical UL/Output Current, Light-Overload Use (UL)":"77 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":null,"alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50000271160/alternatives.json"},"ai":{"faq":[{"question":"What is the frame size on the 3AXD50000271160?","answer":"The 3AXD50000271160 ships in an R5 frame."},{"question":"What supply frequency does the 3AXD50000271160 accept?","answer":"The drive runs on 50/60 Hz supply."},{"question":"What are the UL output ratings on the 3AXD50000271160?","answer":"UL light-overload use is rated 75 Hp at 77 A; UL heavy-duty use is rated 60 Hp at 62 A."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50000271160","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50000271160 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:21:01.794Z","lastPublished":"2026-09-02T08:21:01.794Z","indexable":true}}