{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50000275441","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50000275441","canonicalUrl":"https://aoctrl.com/abb/3AXD50000275441","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50000275441","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACH480-04-03A4-4, LV AC drive module for HVAC, 1.1 kW, 3.3 A, 400 V, frame R1, IP20, BACnet.","salesMarkdown":"The ABB 3AXD50000275441 is an ACH480-04-03A4-4 LV AC drive module built for HVAC duty. It delivers 1.1 kW normal-use output at 3.3 A from a 380–480 V three-phase supply, frame size R1, IP20 open type. The drive includes the control unit, so it's ready for panel integration out of the box. ## Ratings and duty cycles Normal-use output is 1.1 kW at 3.3 A; light-overload use holds at 1.1 kW, 3.1 A. Heavy-duty use derates to 0.75 kW, 2.6 A — that's the number to size against if the load profile includes frequent starts or peak torque demands. UL-listed output currents are slightly lower: 3 A normal-use, 2.1 A heavy-duty, 3.0 A light-overload. Apparent power output is 2.3 kVA. Standby loss sits at 15 W; full-load power consumption is 55 W. BACnet is the onboard protocol — no option card needed for BMS integration. Two analog inputs and two analog outputs, plus six digital inputs and three digital outputs. That's enough for a basic AHU or pump controller without adding remote I/O. ## Physical and environmental Sound level is 63.1 dB(A). The module includes a CR2032 lithium coin cell (220 mAh, 3 V) for real-time clock backup. Frequency range is 47.5–63 Hz.","metaTitle":"ABB 3AXD50000275441 ACH480-04-03A4-4 Drive, 1.1 kW, 3.3 A","metaDescription":"ABB ACH480-04-03A4-4 LV AC drive module for HVAC, 1.1 kW, 3.3 A, 400 V, active production. BACnet, IP20, frame R1. RoHS/REACH compliant. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"SCIP":"4b7f0af1-4313-4811-b990-f45b6c1653c8 Finland","Includes":"Control unit","Frame Size":"R1","Sound dB (A)":"63.10 dB(A)","Standby Loss":"15 W","Analog Inputs":"2","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Module","WEEE Category":"5. Small Equipment (No External Dimension More Than 50 cm)","Analog Outputs":"2","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Temperature Rating":"Maximum 50 °C","Enclosure Type NEMA":"Open Type","Input Voltage (Uin)":"380 ... 480 V","Degree of Protection":"IP20","Apparent Power Output":"2.3 kV·A","Communication Protocol":"BACNET","Power Consumption (@Pcons)":"55 W","Multiple Battery Information":"Lithium Coin, CR2032, 220 mAh, 3 V, 1 pc, 3 g","Number of Digital In/Outputs":"6 / 3","Number of Hardware Interfaces":"Industrial Ethernet 0","Output Power, Normal Use (Pn)":"1.1 kW","Output Current, Normal Use (In)":"3.3 A","Output Power, Heavy-Duty Use (PhD)":"0.75 kW","Output Current, Heavy-Duty Use (IhD)":"2.6 A","Output Power, Light-Overload Use (PlD)":"1.1 kW","Certificates and Declarations/RoHS Date":"20230315","Certificates and Declarations/REACH Date":"20250905","Output Current, Light-Overload Use (IlD)":"3.1 A","Technical UL/Output Current, Normal Use (UL)":"3 A","Certificates and Declarations/RoHS Information":"Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019","Certificates and Declarations/REACH Information":"True - contains substances > 0.1 mass percentage","Technical UL/Output Current, Heavy-Duty Use (UL)":"2.1 A","Technical UL/Output Current, Light-Overload Use (UL)":"3.0 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50000275441","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50000275441/alternatives.json"},"ai":{"faq":[{"question":"What compliance documentation does this drive carry?","answer":"RoHS compliant per EU Directive 2011/65/EU and Amendment 2015/863 (date 20230315). REACH declaration confirms substances above 0.1 mass percentage (date 20250905). SCIP number is 4b7f0af1-4313-4811-b990-f45b6c1653c8 Finland."},{"question":"What are the key output ratings for this drive?","answer":"Normal-use output is 1.1 kW at 3.3 A; heavy-duty use derates to 0.75 kW at 2.6 A. UL-listed normal-use output is 3 A."},{"question":"Does this drive include the control unit?","answer":"Yes, the listing includes the control unit — it's a complete drive module, not a power stage alone."},{"question":"What communication protocol does it support?","answer":"BACnet is the onboard protocol, suitable for direct BMS integration without an additional option card."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50000275441","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50000275441 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}