{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50000275489","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50000275489","canonicalUrl":"https://aoctrl.com/abb/3AXD50000275489","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50000275489","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACH480-04 LV AC drive module, 3-phase 380-480 V input, 4 kW / 9.4 A normal-use output, IP20, BACnet, frame size R1.","salesMarkdown":"The ABB 3AXD50000275489 is a low-voltage AC drive module for HVAC, rated 4 kW normal-use output at 9.4 A on a 400 V three-phase supply. It ships as a control unit included in frame size R1, with IP20 open-type enclosure. Input accepts 380 to 480 V, 47.5 to 63 Hz, three-phase. Normal-use output current is 9.4 A; heavy-duty use drops to 7.2 A at 3.0 kW. Light-overload use is rated 8.9 A at 4.0 kW. UL-listed output currents are slightly lower: 7.6 A normal-use, 4.8 A heavy-duty, 7.6 A light-overload. Built-in BACnet communication is standard, with 2 analog inputs, 2 analog outputs, and 6 digital inputs / 3 digital outputs. Standby loss is 15 W; typical power consumption under load is 140 W. Efficiency meets IE2 level. Rated for maximum 50 °C ambient. Sound level is 63.1 dB(A). The module contains a lithium coin cell (CR2032, 220 mAh, 3 V) for real-time clock backup.","metaTitle":"ABB 3AXD50000275489 ACH480-04 Drive Module, 4 kW, 9.4 A, 400","metaDescription":"ABB ACH480-04 drive module, 4 kW normal-use, 9.4 A output, 380-480 V 3-phase. BACnet, IP20, active production. RoHS/REACH compliant. RFQ for lead time.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"SCIP":"4b7f0af1-4313-4811-b990-f45b6c1653c8 Finland","Includes":"Control unit","Frame Size":"R1","Sound dB (A)":"63.10 dB(A)","Standby Loss":"15 W","Analog Inputs":"2","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Module","WEEE Category":"5. Small Equipment (No External Dimension More Than 50 cm)","Analog Outputs":"2","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Temperature Rating":"Maximum 50 °C","Enclosure Type NEMA":"Open Type","Input Voltage (Uin)":"380 ... 480 V","Degree of Protection":"IP20","Apparent Power Output":"6.5 kV·A","Communication Protocol":"BACNET","Power Consumption (@Pcons)":"140 W","Multiple Battery Information":"Lithium Coin, CR2032, 220 mAh, 3 V, 1 pc, 3 g","Number of Digital In/Outputs":"6 / 3","Number of Hardware Interfaces":"Industrial Ethernet 0","Output Power, Normal Use (Pn)":"4 kW","Output Current, Normal Use (In)":"9.4 A","Output Power, Heavy-Duty Use (PhD)":"3.0 kW","Output Current, Heavy-Duty Use (IhD)":"7.2 A","Output Power, Light-Overload Use (PlD)":"4.0 kW","Certificates and Declarations/RoHS Date":"20230315","Certificates and Declarations/REACH Date":"20250905","Output Current, Light-Overload Use (IlD)":"8.9 A","Technical UL/Output Current, Normal Use (UL)":"7.6 A","Certificates and Declarations/RoHS Information":"Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019","Certificates and Declarations/REACH Information":"True - contains substances > 0.1 mass percentage","Technical UL/Output Current, Heavy-Duty Use (UL)":"4.8 A","Technical UL/Output Current, Light-Overload Use (UL)":"7.6 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50000275489","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50000275489/alternatives.json"},"ai":{"faq":[{"question":"What compliance documentation does this drive module carry?","answer":"RoHS compliant per EU Directive 2011/65/EU and amendment 2015/863. REACH declaration confirms substances above 0.1% mass. SCIP number is 4b7f0af1-4313-4811-b990-f45b6c1653c8 Finland."},{"question":"What are the key output ratings for this ACH480-04 drive?","answer":"Normal-use: 4 kW, 9.4 A. Heavy-duty: 3.0 kW, 7.2 A. Light-overload: 4.0 kW, 8.9 A. UL-listed normal-use: 7.6 A."},{"question":"What communication protocol is built in?","answer":"BACnet is standard on this module. No additional hardware interface for Industrial Ethernet is included."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50000275489","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50000275489 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}