{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50000296767","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50000296767","canonicalUrl":"https://aoctrl.com/abb/3AXD50000296767","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50000296767","rawCanonicalId":null},"summary":{"shortDescription":"ABB, ACH580 series, LV AC wall-mounted HVAC drive, 3AXD50000296767, Frame Size R2, 24.2 A output, 208–240 V, IP55.","salesMarkdown":"The 3AXD50000296767: Rated for IP55 and NEMA Type 12 enclosures, meaning it handles dust, hose-down, and the kind of wet mechanical-room floors you find in commercial HVAC. The R2 frame keeps the footprint manageable for wall-mounting without a dedicated cabinet. ## Ratings that matter for the install Standby loss sits at 14 W — low enough that you don't need to factor extra ventilation for idle time, but not negligible if you're counting every watt on a battery-backed bus. Ambient temperature is capped at 40 °C for full rating. Above that you derate per the drive's thermal curve — standard for any wall-mount unit in a warm mechanical room.","metaTitle":"ABB 3AXD50000296767 ACH580-01 HVAC Drive, 24.2 A, R2 Frame","metaDescription":"ABB ACH580-01-024A-2+B056 HVAC drive, 24.2 A, 208–240 V, IP55, Type 12, IE2. Active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 240V"],"specifications":{"Frame Size":"R2","Standby Loss":"14 W","Frequency (f)":"50/60 Hz","Mounting Type":"Wall-mounting","WEEE Category":"4. Large Equipment (Any External Dimension More Than 50 cm)","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Temperature Rating":"Maximum 40 °C","Enclosure Type NEMA":"Type12","Input Voltage (Uin)":"208 ... 240 V","Degree of Protection":"IP55","Apparent Power Output":"9.6 kV·A","Output Current, Normal Use (In)":"24.2 A","Output Power, Light-Overload Use (PlD)":"7.5 Hp"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50000296767","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50000296767/alternatives.json"},"ai":{"faq":[{"question":"What is the standby power loss?","answer":"14 W in standby — low enough to skip forced cooling in most cabinets, but worth counting in a tight power budget."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50000296767","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50000296767 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}