{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50000296798","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50000296798","canonicalUrl":"https://aoctrl.com/abb/3AXD50000296798","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50000296798","rawCanonicalId":null},"summary":{"shortDescription":"ABB, ACH580-01 series, LV AC wall-mounted drive, 3AXD50000296798, 59.4 A, 208-240 V, IP55, Type 12, Frame R3.","salesMarkdown":"The 3AXD50000296798: The drive is housed in a NEMA Type 12 enclosure with IP55 protection, rated for wall-mounting. Frame size is R3, and standby loss runs 15 W. It is rated IE2 efficiency and operates on 50/60 Hz supply. Maximum ambient temperature is 40 °C. The 59.4 A normal-use output current is the figure to match against your motor full-load amps. The light-overload rating of 20 Hp gives headroom for pump and fan curves that don't exceed that power level. IP55 and Type 12 enclosure means it's suitable for indoor environments with dust and dripping water — typical for HVAC mechanical rooms or light industrial plant floors. Wall-mounting keeps it off the floor, but verify the R3 frame dimensions against your panel layout. Standby loss of 15 W is modest; it won't drive up cooling requirements in a closed cabinet, but it's not zero — account for it in your thermal budget if the drive is in a sealed enclosure.","metaTitle":"ABB 3AXD50000296798 ACH580-01 VFD, 59.4 A, 208-240 V","metaDescription":"ABB ACH580-01-059A-2+B056 LV AC wall-mounted drive, 59.4 A output, 208-240 V 3-phase, IP55, Type 12 enclosure. Active production, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 240V"],"specifications":{"Frame Size":"R3","Standby Loss":"15 W","Frequency (f)":"50/60 Hz","Mounting Type":"Wall-mounting","WEEE Category":"4. Large Equipment (Any External Dimension More Than 50 cm)","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Temperature Rating":"Maximum 40 °C","Enclosure Type NEMA":"Type12","Input Voltage (Uin)":"208 ... 240 V","Degree of Protection":"IP55","Apparent Power Output":"24 kV·A","Output Current, Normal Use (In)":"59.4 A","Output Power, Light-Overload Use (PlD)":"20 Hp"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50000296798","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50000296798/alternatives.json"},"ai":{"faq":[{"question":"What is the frame size of the 3AXD50000296798?","answer":"The frame size is R3."},{"question":"What is the standby loss of this drive?","answer":"Standby loss is 15 W."},{"question":"What is the output current rating?","answer":"Normal-use output current is 59.4 A, with a light-overload power rating of 20 Hp."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50000296798","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50000296798 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}