{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50000296842","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50000296842","canonicalUrl":"https://aoctrl.com/abb/3AXD50000296842","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50000296842","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACH580-01 series, LV AC wall-mounted HVAC drive, 3AXD50000296842, 169 A, 208-240 V, IP55, IE2.","salesMarkdown":"The 3AXD50000296842: The light-overload output is 60 Hp, which tells you the drive can handle a 60 Hp motor on a fan or pump curve without derating. The apparent power output of 67 kVA gives you the transformer sizing reference for the input side. Standby loss of 22 W is low enough that ventilation in a small electrical room won't be an issue, but it's not zero — factor it into the panel heat budget if you're stacking multiple drives. Wall-mounting with a NEMA Type 12 / IP55 enclosure means it's dust-tight and hose-down resistant — suitable for washdown areas or dusty HVAC mechanical rooms. Maximum ambient temperature 40 °C; if your room runs hotter, you'll need to derate or add forced cooling. The WEEE Category 4 classification is a disposal note for end-of-life recycling, not a performance spec.","metaTitle":"ABB 3AXD50000296842 ACH580-01 HVAC Drive, 169 A, IP55","metaDescription":"ABB 3AXD50000296842 ACH580-01 wall-mounted HVAC drive, 169 A output, 208-240 V 3-phase, IP55, IE2, active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 240V"],"specifications":{"Frame Size":"R7","Standby Loss":"22 W","Frequency (f)":"50/60 Hz","Mounting Type":"Wall-mounting","WEEE Category":"4. Large Equipment (Any External Dimension More Than 50 cm)","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Temperature Rating":"Maximum 40 °C","Enclosure Type NEMA":"Type12","Input Voltage (Uin)":"208 ... 240 V","Degree of Protection":"IP55","Apparent Power Output":"67 kV·A","Output Current, Normal Use (In)":"169 A","Output Power, Light-Overload Use (PlD)":"60 Hp"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50000296842","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50000296842/alternatives.json"},"ai":{"faq":[{"question":"What is the frame size of this drive?","answer":"Frame size R7. That determines the physical footprint and mounting hole pattern for the wall-mount bracket."},{"question":"What is the standby power loss?","answer":"22 W. This is the power the drive consumes when the motor is stopped but the drive is still powered — useful for panel heat calculations."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50000296842","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50000296842 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}