{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50000296859","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50000296859","canonicalUrl":"https://aoctrl.com/abb/3AXD50000296859","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50000296859","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACH580-01-211A-2+B056, LV AC wall-mounted drive for HVAC, 211 A, 208-240 V, IP55, NEMA 12, IE2.","salesMarkdown":"The 3AXD50000296859 is an ABB ACH580-01 HVAC drive in frame size R7, wall-mounted, rated for 211 A normal use on a 208-240 V three-phase supply. That output current supports light-overload motor loads up to 75 Hp. The 84 kVA apparent power rating gives the headroom needed for fan and pump starts without oversizing the drive. IP55 and NEMA Type 12 enclosure means the drive is sealed against dust and low-pressure water jets — suitable for washdown areas or outdoor installations under a roof. Maximum ambient temperature is 40 °C; above that, derate the output current per the drive's thermal curve. The wall-mounting footprint for frame R7 requires a flat, rigid surface with clearance for the cooling fins and cable entry glands. ## Efficiency and standby Rated IE2 efficiency class — this is the standard for HVAC drives in most regions; no premium-efficiency premium here. Standby loss is 22 W, which matters for continuous-operation installations where the drive idles between duty cycles. The drive operates on 50/60 Hz supply without configuration changes.","metaTitle":"ABB 3AXD50000296859 ACH580-01 HVAC Drive, 211 A, 208-240 V","metaDescription":"ABB ACH580-01-211A-2+B056 LV AC wall-mounted drive for HVAC, 211 A output, 208-240 V input, IP55, NEMA 12, IE2. Active production.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 240V"],"specifications":{"Frame Size":"R7","Standby Loss":"22 W","Frequency (f)":"50/60 Hz","Mounting Type":"Wall-mounting","WEEE Category":"4. Large Equipment (Any External Dimension More Than 50 cm)","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Temperature Rating":"Maximum 40 °C","Enclosure Type NEMA":"Type12","Input Voltage (Uin)":"208 ... 240 V","Degree of Protection":"IP55","Apparent Power Output":"84 kV·A","Output Current, Normal Use (In)":"211 A","Output Power, Light-Overload Use (PlD)":"75 Hp"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50000296859","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50000296859/alternatives.json"},"ai":{"faq":[{"question":"What is the frame size and what does it mean for mounting?","answer":"Frame size R7. This is a wall-mounted drive requiring a flat surface with adequate clearance for cooling and cable entry. The physical dimensions are consistent with the R7 frame in the ACH580 family."},{"question":"What is the standby power loss?","answer":"Standby loss is 22 W. This is the power dissipated when the drive is powered but not running a motor — relevant for energy-conscious installations or UPS-backed systems."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50000296859","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50000296859 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}