{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50000417681","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50000417681","canonicalUrl":"https://aoctrl.com/abb/3AXD50000417681","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50000417681","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACH580-01-018A-2, LV AC wall-mounted HVAC drive, 4 kW / 16.9 A normal use, 200-240 V 3-phase, IP21, BACnet, frame R1.","salesMarkdown":"The 3AXD50000417681: Normal-use output current (In) is 16.9 A — that's the continuous rating for a 4 kW motor on a standard fan or pump curve. Heavy-duty use (IhD) drops to 10.6 A at 3.0 kW, which governs constant-torque loads like conveyors or compressors. The drive carries an IE2 efficiency level, and standby loss is 13 W — relevant for continuous-running installations where idle power matters. Communication is BACnet over the built-in interface — no Industrial Ethernet port on this variant (0 hardware interfaces for that protocol). Analog I/O is 2 inputs and 2 outputs; digital I/O is 6 inputs and 3 outputs. The BACnet stack is preloaded, so no option card is needed for BMS integration. Wall-mounted, frame size R1. Ambient temperature is rated to 40 °C maximum; altitude to 1000 m without derating. Sound level is 59 dB(A) — typical for this power class, not silent but acceptable in a mechanical room.","metaTitle":"ABB 3AXD50000417681 ACH580-01 VFD, 4 kW, 16.9 A, 230 V","metaDescription":"ABB ACH580-01-018A-2 HVAC drive, 4 kW normal use, 16.9 A output, 200-240 V 3-phase, IP21, BACnet, active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 240V"],"specifications":{"SCIP":"8105d671-49fa-4c1c-836d-baf56982886a Finland","Altitude":"1000 m","Includes":"Control unit","Frame Size":"R1","Sound dB (A)":"59 dB(A)","Standby Loss":"13 W","Analog Inputs":"2","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Wall-mounted","WEEE Category":"5. Small Equipment (No External Dimension More Than 50 cm)","Analog Outputs":"2","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Temperature Rating":"Maximum 40 °C","Enclosure Type NEMA":"Type1","Input Voltage (Uin)":"200 ... 240 V","Degree of Protection":"IP21","Apparent Power Output":"7.2 kV·A","Communication Protocol":"BACNET","Power Consumption (@Pcons)":"230 W","Operating Humidity (RHamβ)":"95","Multiple Battery Information":"Lithium Coin, CR2032, 220 mAh, 3 V, 1 pc, 3 g","Number of Digital In/Outputs":"6 / 3","Number of Hardware Interfaces":"Industrial Ethernet 0","Output Power, Normal Use (Pn)":"4 kW","Output Current, Normal Use (In)":"16.9 A","Output Power, Heavy-Duty Use (PhD)":"3.0 kW","Output Current, Heavy-Duty Use (IhD)":"10.6 A","Output Power, Light-Overload Use (PlD)":"4.0 kW","Certificates and Declarations/RoHS Date":"20240508","Certificates and Declarations/REACH Date":"20250905","Output Current, Light-Overload Use (IlD)":"16.7 A","Certificates and Declarations/RoHS Information":"Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019","Certificates and Declarations/REACH Information":"True - contains substances > 0.1 mass percentage"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50000417681","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50000417681/alternatives.json"},"ai":{"faq":[{"question":"What compliance documentation is available for this drive?","answer":"RoHS compliance is declared per EU Directive 2011/65/EU and Amendment 2015/863 (RoHS date 20240508). REACH information confirms the product contains substances above 0.1% mass percentage (REACH date 20250905). The SCIP number is 8105d671-49fa-4c1c-836d-baf56982886a Finland."},{"question":"What is the altitude rating for this drive?","answer":"The drive is rated for installation at altitudes up to 1000 m without derating."},{"question":"What communication protocol does this drive support?","answer":"BACnet is the listed communication protocol. There are no Industrial Ethernet hardware interfaces on this variant."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50000417681","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50000417681 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}